发变组转子绕组过负荷保护与励磁调节器过励限制保护正确的动作配合关系,应该是励磁调节器过励限制保护先于发变组转子绕组过负荷保护动作。通过对四方CSC-300F发变组转子绕组过负荷保护与Unitrol 5000励磁调节器过励磁限制动作值与动作时间的计算与分析,指出过励磁限制保护设计上存在的缺陷并提出解决方法。
Abstract:The over-excitation limitation protection of excitation regulator should occur before the overload protection of generator-transformer unit rotor winding in the correct action cooperation between the overload protection and over-excitation limitation.Through the calculation and analysis of the action values and time of the overload protection of CSC-300F generator-transformer unit rotor winding and the over-excitation limitation of Unitrol 5000 excitation regulator,this paper puts forward the defects in the design of over-excitation limitation protection as well as the solutions.
王维俭.电气主设备继电保护原理与应用[M].北京:中国电力出版社,2001.
GB/T 14285-2006继电保护和安全自动装置技术规程[S].北京:中国电力出版社,2006.
GB/T 74093-2007同步电机励磁系统及大、中型同步发电机励磁系统技术要求[S].北京:中国电力出版社,2007.
基本信息:
DOI:10.19585/j.zjdl.2012.07.007
中图分类号:TM303.3
引用信息:
[1]黄龙,方昌勇,胡凯波.励磁调节器过励限制与发电机转子绕组过负荷保护的整定配合分析[J],2012,31(07):21-23.DOI:10.19585/j.zjdl.2012.07.007.