特高压GIS特高频内置传感器有效监测范围现场测试与评估技术研究Research on Field Test and Evaluation Technique for Effective Monitoring Range of the UHF Built-in Sensor of UHV GIS
邵先军,何文林,王绍安,徐华,吴胥阳,刘浩军,周阳洋
SHAO Xianjun,HE Wenlin,WANG Shaoan,XU Hua,WU Xuyang,LIU Haojun,ZHOU Yangyang
摘要(Abstract):
为有效评估特高压GIS特高频内置传感器的灵敏度及其监测范围,搭建了252 k V GIS等效脉冲注入实验平台。首先通过等效实验方法,建立252 k V GIS内典型缺陷5 p C放电量与等效注入脉冲信号波形之间的关系;结合252 k V GIS和1 100 k V GIS的特高频电磁波数值计算,仿真得到了1 100k V GIS内缺陷5 p C放电量下的等效注入脉冲信号的波形参数。针对特高压某站1 100 k V GIS的各种典型特高频传感器布置方式,开展有效监测范围的现场测试与评估,结果表明:特高压安吉站1 100k V GIS只有出线间隔布置方式的B相满足监测灵敏度的要求。最后提出特高频内置传感器优化布置计算方法,并依此提出了特高压某站1 100 k V GIS的特高频内置传感器优化布置方案。
In order to evaluate the sensitivity and monitoring range of UHF built-in sensor of UHV GIS, an equivalent impulse injection experimental platform of 252 k V GIS was established. Through the equivalent experiment method, relationship between the defective discharge capacity of 5 p C and equivalent impulse injection signal wave was established; according to values calculation of UHF electromagnetic wave of 252 k V and1 100 k V GIS, parameter of the equivalent impulse injection signal wave with the defective discharge capacity of 5 p C in 1 100 k V GIS was concluded by simulation. In accordance to the distribution mode of various typical UHF sensors in 1 100 k V GIS in a UHV substation, field test and evaluation on the effective monitoring range were conducted. The result shows that only phase B in alternative arrangement of 1 100 k V GIS in Anji UHV substation meets the monitoring sensitivity requirement. At the last, the paper presents an optimized arrangement and calculation method for UHF built-in sensors and thereof proposes an optimized arrangement scheme for UHF built-in sensor in 1 100 k V GIS in an UHV substation.
关键词(KeyWords):
特高频传感器;等效注入脉冲;优化布置;现场测试
UHF sensor;equivalent impulse injection;optimized arrangement;field test
基金项目(Foundation): 国家自然科学基金(51607140);; 国网浙江省电力公司科技项目(5211DS15002P)
作者(Author):
邵先军,何文林,王绍安,徐华,吴胥阳,刘浩军,周阳洋
SHAO Xianjun,HE Wenlin,WANG Shaoan,XU Hua,WU Xuyang,LIU Haojun,ZHOU Yangyang
DOI: 10.19585/j.zjdl.201711003
参考文献(References):
- [1]M D JUDD,O FARISH,B F HAMPTON.The Excitation of UHF signal by partial discharge in GIS[J].IEEE Transac tions on Dielectrics and Electrical Insulation,1996,3(2):213-228.
- [2]S OKABE,S KANEKO,M YOSHIMURA,et al.Partial Discharge Diagnosis Method Using Electromagnetic Wave Mode Transformation in Gas Insulated Switchgear[J].IEEETransactions on Dielectrics and Electrical Insulation,2007,14(3):702-709.
- [3]李军浩,韩旭涛,刘泽辉,等.电气设备局部放电检测技术述评[J].高电压技术,2015,41(8):2583-2601.
- [4]汲胜昌,王圆圆,李军浩.GIS局部放电检测用特高频天线研究现状及发展[J].高压电器,2015,51(4):163-172.
- [5]MARTIN D,JUDD,OWEN FARISH.A Pulsed GTEM System for UHF Sensor Calibration[J].IEEE Transactions on Instrumentation and Measurement,1998,47(4):875-880.
- [6]李端姣,唐志国.GIS局部放电特高频检测系统标定研究[J].高电压技术,2015,41(10):3348-3354.
- [7]U SCHICHLER,W KOLTUNOWICZ,F ENDO,et al.Risk Assessment on Defects in GIS Based on PD Diagnostics[J].IEEE Transactions on Dielectrics and Electrical Insulation,2013,20(6):2165-2172.
- [8]TOSHIHIRO HOSHINO,KATSUMI KATO,NAOKI HAYAKAWA,et al.Frequency Characteristics of Electromagnetic Wave Radiated From GIS Apertures[J].IEEE Transactions on Power Delivery,2001,16(4):552-557.
- [9]JUDD M D,YANG L,HUNTER I B.Partial discharge monitoring of power transformers using UHF sensors.Part I:sensors and signal interpretation[J].IEEE Electr Insul Mag,2005,21(2):5-14.
- [10]CIGRE TF 15/33 03 05.Partial discharge detection system GIS:Sensitivity verification UHF method method[J].Electra,1999(183):74-87.