10kV配电装置母分间隔防误回路的改进Improvement of Anti-Maloperation Circuit of Busbar Sectional Separate Unit of 10 kV Distribution Device
谢明海,吕亮,陈瑛,张旭阳,朱松涛
XIE Minghai,LYU Liang,CHEN Ying,ZHANG Xuyang,ZHU Songtao
摘要(Abstract):
配电装置的防误操作闭锁回路能有效防止误操作事故的发生,当母分隔离小车处在"试验"与"运行"位置之间的自由位置(既不在试验位置,也不在工作位置,而是在中间位置)时分合断路器,会引起触头拉弧而导致事故,因此母分间隔的防误回路中有必要增加"母分隔离小车在自由位置时,闭锁断路器合闸"的功能。通过分析现行的母分间隔电气防误回路,根据10 k V金属铠装移开式开关柜的结构特点,提出"在合闸回路中实现开关闭锁功能"和"固定操作顺序实现开关闭锁功能"2种改进方法,从而完善母分间隔的防误回路,能有效地消除事故隐患。
The anti-maloperation locking circuit of the power distribution device can effectively prevent the occurrence of the maloperation accident.When the busbar split car is at the free position between the "test" and "run",the circuit breaker operation can cause accident due to arc between contactors.Therefore,the antimaloperation circuit of the busbar sectional unit is necessary to increase the function of "locking the breaker when the busbar split trolley is in the free position(the trolley is neither in the test position nor in the work position,but in the middle position)".Through analyzing the anti-maloperation electric interlocking circuit of the power distribution device,the paper indicates the shortage of anti-maloperation circuit.According to the structural characteristics of 10 k V metal clad withdrawable switch cabinet,the paper proposes " increasing switch locking function in the closing loop" and "fixing operation sequence to actualize switch interlocking function" to perfect anti-maloperation circuit of busbar sectional separate unit and eliminate hidden hazards.
关键词(KeyWords):
防误操作;电气联锁;配电装置;开关闭锁
anti-maloperation;electrical interlocking;power distribution device;switch blocking
基金项目(Foundation):
作者(Author):
谢明海,吕亮,陈瑛,张旭阳,朱松涛
XIE Minghai,LYU Liang,CHEN Ying,ZHANG Xuyang,ZHU Songtao
DOI: 10.19585/j.zjdl.2017.01.001
参考文献(References):
- [1]防止电气误操作装置管理规定[M].北京:中国电力出版社,2003.
- [2]顾拥军,皮卫华,杨乘胜,等.变电站防误装置应用分析[J].继电器,2005(33):66.
- [3]DL/T 969-2005变电站运行导则[S].北京:中国电力出版社,2006.
- [4]Q/GDW 11-154-2009 110~500 k V变电所防误操作闭锁逻辑规范[S].杭州:浙江省电力公司,2009.
- [5]Q/SDJ 1050201-2007微机五防装置闭锁逻辑编写与安装标准[S].杭州:浙江省电力公司,2007.
- [6]国家电网公司基建部.国家电网公司输变电工程通用设计110(66)~220 k V智能变电站施工图设计(2013版)[M].北京:中国电力出版社,2013.
- [7]章恩科.6 k V开关柜操作回路的分析与改进[J].浙江电力,2015,34(6):49-51.
- [8]吕理想,应军,陈红敏,等.110 k V特殊内桥双线单主变接线及其备自投运行方式探讨[J].浙江电力,2014,33(01):64-68.
- [9]赵玉成,姚剑峰,金山红,等.状态检修模式下隔离开关异常操作预案的创新与实践[J].浙江电力,2015,34(8):21-24.