智能变电站PMU频率跳变问题的诊断及处理Diagnosis and treatment for frequency hopping of PMU within an intelligent substation
王志华,张江南,晋阳珺,徐志伟,吴坡,李晓辉,杨芊芊
WANG Zhihua,ZHANG Jiangnan,JIN Yangjun,XU Zhiwei,WU Po,LI Xiaohui,YANG Qianqian
摘要(Abstract):
某省区WAMS(广域测量系统)中某智能变电站数字化PMU(相量测量单元)偶尔出现频率跳变现象。首先,调取频率跳变时刻的动态数据记录和录波文件,结合现场运行方式进行分析,得出两次频率跳变事件的原因。然后,通过调整智能终端模拟量阈值、改进SV(采样值)组网模式、划分交换机VLAN(虚拟局域网)、调整装置带宽阈值,解决了SV丢点造成的频率波动;同时对SV补点提升PMU装置SV异常容错能力,丢帧数小于3不会造成频率波动超限。接着,查找现场扰动源,分析扰动造成PMU频率波动的原因,提出基于触发录波文件的扰动快速识别方法。最后,通过实验验证了所提方法的有效性。
In the wide area measurement system(WAMS) of a province, occasional frequency hopping has been observed in digital phasor measurement unit(PMU) within an intelligent substation. Firstly, dynamic data records and waveform files are retrieved during instances of frequency hopping. Analysis is conducted in conjunction with on-site operational mode, and the causes behind two instances of frequency hopping are figured out. Subsequently, adjustments are made to the analog threshold values of the smart terminal, improvements are implemented in the sampling value(SV) network mode, virtual local area network(VLAN) switches are partitioned, and bandwidth thresholds of the device are fine-tuned to address frequency fluctuations caused by SV packet loss. Moreover, SV data recovery is conducted to enhance the fault tolerance of the PMU, ensuring that a loss of fewer than 3 frames will not lead to frequency fluctuation limit. Furthermore, efforts are made to identify on-site disturbance sources and analyze the causes of disturbances leading to frequency fluctuations in the PMU. A rapid disturbance identification method based on triggering waveform files is proposed. Finally, the effectiveness of the proposed method is validated through experimentation.
关键词(KeyWords):
智能变电站;PMU;频率跳变;SV丢点;扰动;组网
intelligent substation;PMU;frequency hopping;SV packet loss;disturbance;networking
基金项目(Foundation): 国家重点研发计划(2021YFB2401003);; 国网河南省电力公司科技项目(521702230004)
作者(Author):
王志华,张江南,晋阳珺,徐志伟,吴坡,李晓辉,杨芊芊
WANG Zhihua,ZHANG Jiangnan,JIN Yangjun,XU Zhiwei,WU Po,LI Xiaohui,YANG Qianqian
DOI: 10.19585/j.zjdl.202407005
参考文献(References):
- [11]汪芙平,黄松岭,赵伟,等.基于最优线性滤波的PMU测量Ⅰ:最优滤波原理[J].中国电机工程学报,2018,38(8):2262-2271.WANG Fuping,HUANG Songling,ZHAO Wei,et al.PMU measurement based on optimal filteringⅠ:fundamental theory[J].Proceedings of the CSEE,2018,38(8):2262-2271.
- [2]段刚,严亚勤,谢晓冬,等.广域相量测量技术发展现状与展望[J].电力系统自动化,2015,39(1):73-80.DUAN Gang,YAN Yaqin,XIE Xiaodong,et al.Development status quo and tendency of wide area phasor measuring technology[J]. Automation of Electric Power Systems,2015,39(1):73-80.
- [3]李宝伟,文明浩,李宝潭,等.新一代智能变电站SV直采和GOOSE共口传输方案研究[J].电力系统保护与控制,2014,42(1):96-101.LI Baowei,WEN Minghao,LI Baotan,et al.Research of the scheme for SV direct sampling and GOOSE transmit in the same port in new generation smart substation[J].Power System Protection and Control,2014,42(1):96-101.
- [4]国家能源局.电力自动化通信网络和系统第9-2部分:特定通信服务映射(SCSM)-基于ISO/IEC 8802-3的采样值:DL/T 860.92—2016[S].北京:中国电力出版社,2016.
- [5]张江南,雷江龙,贺勇,等.基于PMU误差校正的输电线路参数在线辨识方法[J].电力系统保护与控制,2022,50(19):130-137.ZHANG Jiangnan,LEI Jianglong,HE Yong,et al.Transmission line parameter identification method based on PMU error correction[J]. Power System Protection and Control,2022,50(19):130-137.
- [6]孔祥玉,张烜墉,王成山,等.复杂形态下的配电网自适应自趋优状态估计方法[J].中国电机工程学报,2021,41(10):3339-3348.KONG Xiangyu,ZHANG Xuanyong,WANG Chengshan, et al. Adaptive self-optimizing state estimation method of distribution network in complex condition[J].Proceedings of the CSEE,2021,41(10):3339-3348.
- [7]岳雷,薛安成,李志强,等.水轮发电机调速系统对超低频振荡的影响及模型适用性分析[J].中国电机工程学报,2019,39(1):227-235.YUE Lei,XUE Ancheng,LI Zhiqiang,et al. Effects on extra-low frequency oscillation caused by hydro generator governor system and model suitability analysis[J]. Proceedings of the CSEE,2019,39(1):227-235.
- [8]李子康,刘灏,毕天姝,等.基于数据驱动的鲁棒性电力系统扰动识别[J].中国电机工程学报,2021,41(21):7261-7275.LI Zikang,LIU Hao,BI Tianshu,et al.Data-driven robust power system disturbance identification[J].Proceedings of the CSEE,2021,41(21):7261-7275.
- [9]国家能源局华北监管局.华北区域发电厂并网运行管理实施细则[Z].北京:国家能源局华北监管局,2019.
- [10]国家市场监督管理总局,国家标准化管理委员会.火力发电机组一次调频试验及性能验收导则:GB/T 30370—2022[S].北京:中国标准出版社,2022.
- [11]国家电网有限公司.电力系统实时动态监测系统技术规范:Q/GDW 10131—2012[S].北京:中国电力出版社,2017.
- [12]中国南方电网有限责任公司.相量测量装置(PMU)技术规范:Q/CSG 1203052—2018[S].广州,2018.
- [13] IEC.Measuring relays and protection equipment-Part 118-1:synchrophasor for power systems measurements:IEC/IEEE 60255-118-1 industrial electronics[S]. USA:IEC,2021.
- [14]刘振亚.国家电网公司输变电工程110(66)~750 kV智能变电站部分:2011年版[M].北京:中国电力出版社,2011.
- [15]王志华,杜振华,董志平,等.智能变电站网络风暴抑制技术研究[J].电气工程学报,2016,11(2):40-46.WANG Zhihua,DU Zhenhua,DONG Zhiping,et al.Study of intelligent substation network storm suppression technology[J].Journal of Electrical Engineering,2016,11(2):40-46.
- [16]谢希仁.计算机网络[M].7版.北京:电子工业出版社,2017.
- [17]国家电网有限公司.智能变电站网络交换机技术规范:Q/GDW 1429—2012[S].北京:中国电力出版社,2012.
- [18]毕天姝.广域同步相量测量技术及其应用[M].北京:中国电力出版社,2014.