一起金属氧化物避雷器异常状态诊断与分析Diagnosis and Analysis of a MOA Abnormality
孙林涛,艾云飞,张翾喆,吴承福,李文燕
SUN Lintao,AI Yunfei,ZHANG Xuanzhe,WU Chengfu,LI Wenyan
摘要(Abstract):
MOA(金属氧化物避雷器)因具备良好的非线性伏安特性和通流能力而广泛应用于电力系统中,其长期运行可能会出现发热、绝缘性能下降等缺陷。综合运用阻性电流检测、 HFCT(高频电流互感器)局部放电检测、红外精确测温等带电检测技术对某220 kV MOA进行诊断与分析,通过停电试验和解体检查验证了带电检测结论,发现异常原因是:避雷器内部未充N2或充N2不足造成内部构成负压,下端防爆装置承受向内应力,长期运行后防爆装置向内破裂,造成避雷器内部受潮,绝缘性能下降,最终导致异常发热。
MOA(metal oxide arrester) has good non-linear volt-ampere characteristics and through-flow capacity, and thus is widely used in power system. Heat and insulation performance decline may occur with its long-term operation. In this paper, live resistance current detection, HFCT(high frequency current transformer) PD detection and infrared thermal imaging are used to diagnose and analyze a 220 kV MOA. Living detection conclusion is verified by outage test and disassembling inspection. The reason of the MOA abnormality is that N2 vacancy or insufficient N2 leads to the internal negative pressure; explosion-proof equipment bears inward stress and breaks inwardly after long operation, which causes MOA internal damping, insulation performance decline and finally heat abnormality.
关键词(KeyWords):
金属氧化物避雷器;带电检测;高频电流;红外热成像;阻性电流
MOA;live detection;high frequency current;infrared thermal imaging;resistance current
基金项目(Foundation):
作者(Author):
孙林涛,艾云飞,张翾喆,吴承福,李文燕
SUN Lintao,AI Yunfei,ZHANG Xuanzhe,WU Chengfu,LI Wenyan
DOI: 10.19585/j.zjdl.201908007
参考文献(References):
- [1]罗容波,王岩,李国伟.带电检测技术在避雷器状态诊断中的成功应用[J].电瓷避雷器,2011(6):53-57.
- [2]左文启,顾渊博.220 kV金属氧化物避雷器红外热缺陷及处理分析[J].电瓷避雷器,2010(1):26-28.
- [3]葛猛,韩学坤,陶安培.金属氧化物避雷器阀片老化缺陷的诊断及原因分析[J].高压电器,2009,45(3):145-147.
- [4]段建家,何智强,范敏.一起500 kV金属氧化物避雷器事故分析[J].电瓷避雷器,2014(3):79-83.
- [5]黄松波,黄涛,区伟斌,等.500 kV MOA劣化的带电测试及原因分析[J].高电压技术,2003,29(10):58-59.
- [6]李庆玲,程济兵,张明智.避雷器的常见故障及红外诊断[J].电瓷避雷器,2007(2):30-33.
- [7]刘江明,艾云飞,吴承福,等.金属氧化物避雷器带电检测及异常分析[J].浙江电力,2017,36(3):38-41.
- [8]马丽军,赖靖胤,金鑫磊.一起110 kV氧化锌避雷器运行故障的分析及对策[J].浙江电力,2012,31(8):82-84.
- [9]李红蕾,桑建平,姜伟军,等.浅析MOA泄漏电流测试方法[J].电瓷避雷器,2006(2):40-43.
- [10]带电设备红外诊断应用规范:DL/T 664-2016[S].北京:中国电力出版社,2016.
- [11]交流无间隙金属氧化物避雷器:GB 11032-2010[S].北京:中国标准出版社,2010.
- [12]输变电设备状态检修试验规程:DW 1168-2013[S].北京:中国电力出版社,2013.
- [13]刘安文,许甜田,张少成.带电检测发现金属氧化物避雷器阻性电流异常的案例分析[J].浙江电力,2015,34(6):13-15.
- [14]罗茂嘉,钱珏臻,于军,等.220 kV氧化锌避雷器泄漏电流异常的原因分析和处理[J].浙江电力,2017,36(2):30-33.
- [15]余喆,蓝道林,董树礼,等.一起避雷器泄漏电流异常增大特殊案例分析[J].浙江电力,2018,37(5):38-43.