一起电流二次回路非典型相间短路故障分析Analysis on an Untypical Interphase Short-circuit Fault in Secondary Current Circuit
田洪磊,王一,吕旭东,张松,黄超
TIAN Honglei,WANG Yi,LYU Xudong,ZHANG Song,HUANG Chao
摘要(Abstract):
在一起非典型500 k V线路保护电流二次回路的相间短路故障中,由于短路电阻的存在,导致短路的两相电流出现了换相现象。通过对故障现象进行分析,结合理论计算出短路电阻大小,并借助PSCAD建模加以验证。根据仿真结果分析了短路电阻大小对短路电流的影响,为运维检修人员处理类似缺陷提供了参考。
This paper presents an untypical instance of phase-to-phase short-circuit fault in secondary current fault of 500 k V line protection. During to the short circuit resistance, the phases of the short-circuit current were inverted. By observation and analysis, the value of fault resistance is calculated, and the phenomenon is verified by PSCAD modeling. The influences of short-circuit resistance on short-circuit current is analyzed by simulation result, which can be referenced by operation and maintenance engineers in dealing with similar defects.
关键词(KeyWords):
电流二次回路;相间短路;短路电阻;故障分析;继电保护
secondary current circuit;interphase short circuit;short-circuit resistance;fault analysis;relay protection
基金项目(Foundation):
作者(Author):
田洪磊,王一,吕旭东,张松,黄超
TIAN Honglei,WANG Yi,LYU Xudong,ZHANG Song,HUANG Chao
DOI: 10.19585/j.zjdl.201711002
参考文献(References):
- [1]李显鹏,吴建伟,姜涛,等.一起三相不一致保护误动分析及其回路改进[J].浙江电力,2016,35(5):13-15.
- [2]杨立璠,常宝波.电流互感器二次侧短路故障分析及对策[J].电力自动化设备,2003,23(12):32-33.
- [3]周金刚,刘文玉,周丽萍.两例CT二次电流异常的原因分析及处理[J].电力系统保护与控制,2010,38(15):154-156.
- [4]邱涛,王攀峰,张克元,等.一起二次回路两点接地引起母线保护误动的事故分析[J].电力系统保护与控制,2008,36(24):110-112.
- [5]国家电力调度通信中心.国家电网公司继电保护培训教材[M].北京:中国电力出版社,2009.
- [6]邱关源.电路原理[M].北京:高等教育出版社,2010.
- [7]康权,张鸿飞,吴小波,等.一起二次电压切换回路故障分析[J].浙江电力,2009,28(6):67-69.
- [8]熊小伏,王胜涛,孙鑫,等.一种基于小波的继电保护启动元件性能监测方法[J].电力系统保护与控制,2010,38(24):43-47.
- [9]黄敏,黄淼,彭晓亮.一起线路复杂故障引发越级跳闸的事故分析[J].电力系统自动化,2014,38(5):131-135.
- [10]汤大海,陈永明,曹斌.快速切除220 k V变压器死区故障的继电保护方案[J].电力系统自动化,2014,38(4):115-122.
- [11]王宇,吕旭东,王维振.500 k V电压互感器二次侧过电压的故障分析[J].浙江电力,2017,36(5):20-22.
- [12]王兴国,黄少锋.过渡电阻对故障暂态分量的影响分析[J].电力系统保护与控制,2010,36(2):18-21.
- [13]GIOVANNI MIANO.Transmission Lines and Lumped Circuits[M].San Diego:USA Academic Press,2001.
- [14]何世恩,沈利平.河西750 k V系统故障特征分析及对保护的影响[J].中国电机工程学报,2011,31(S):88-93.
- [15]张东,付豪,王立福,等.一起柔性间隔棒防舞失效案例分析[J].广东电力,2016,29(2):113-115.
- 电流二次回路
- 相间短路
- 短路电阻
- 故障分析
- 继电保护
secondary current circuit - interphase short circuit
- short-circuit resistance
- fault analysis
- relay protection