浙江电力

2013, v.32;No.203(03) 74-76

[打印本页] [关闭]
本期目录(Current Issue) | 过刊浏览(Archive) | 高级检索(Advanced Search)

220kV变压器顶盖连接螺栓发热分析与处理方法
Analysis and Disposal of Connecting Bolt Heating of Head Cover of Main Transformer

段彬,俞军,李传才
DUAN Bin,YU Jun,LI Chuan-cai(Jiaxing Electric Power Bureau

摘要(Abstract):

分析了220 kV变压器顶盖连接螺栓发热的主要原因;介绍了通过将顶盖发热螺栓用铜排直接接地、在螺栓与顶盖间增加绝缘垫片的方式处理顶盖连接螺栓发热故障的方法,测试结果表明对解决变压器顶盖连接螺栓发热具有良好的效果。
The paper analyzes major causes for connecting bolt heating of head cover of 220 kV transformer and introduces the disposal of adding insulation spacer between the bolt and the head cover.The test result shows that the method can effectively handle the connecting bolt heating of head cover of transformer.

关键词(KeyWords): 变压器;漏磁场;螺栓发热
power transformer;stray magnetic field;bolt heating

Abstract:

Keywords:

基金项目(Foundation):

作者(Author): 段彬,俞军,李传才
DUAN Bin,YU Jun,LI Chuan-cai(Jiaxing Electric Power Bureau

DOI: 10.19585/j.zjdl.2013.03.021