水电机组轴电流保护误动原因的分析Cause Analysis on Maloperation of Shaft Current Protection of Hydropower Generating Units
刘小波,傅丽文
LIU Xiao-bo 1,FU Li-wen 2(1.Technical Application Center of Guodian Nanjing Automation Co.
摘要(Abstract):
发电机轴电流对机组危害较大,针对水电机组轴电流保护误报警问题,做了一定的分析和探讨,提出了硬件、软件相结合的滤波措施,以采样基波作为保护判据,消除了低频干扰,现场静态、空载及负荷试验证明效果良好,解决了机组轴电流保护误报警问题。
The shaft current of generator does great harm to units.The paper analyzes and discusses on false alarm of shaft current protection of hydropower generating units and proposes a filtering measure which combines software with hardware.The measure takes the sampled fundamental wave as criteria for protection and eliminates the glitch.The measure turns out to be effective in field static test,no load test and load test and it can handle the false alarm of shaft current protection of units.
关键词(KeyWords):
水电站;轴电流;空间磁场;干扰;滤波
hydropower station;shaft-current;space magnetic field;interference;filtering
基金项目(Foundation):
作者(Author):
刘小波,傅丽文
LIU Xiao-bo 1,FU Li-wen 2(1.Technical Application Center of Guodian Nanjing Automation Co.
DOI: 10.19585/j.zjdl.2012.11.014
参考文献(References):
- 王维俭.电气主设备继电保护原理与应用[M].北京:中国电力出版社,2002.
- 周建为.抽水蓄能机组轴电流保护[J].水电自动化与大坝监测,2003,27(1):68-69.
- 田葳,李树科.发电机轴电流的危害及防范措施[J].电机技术,2004(24):28-29.
- 宁屹,宁峻.发电机上导油槽油色变黑成因分析及处理[J].江西电力,2007,31(2):15-16.
- 刘小波,包明磊.百万机组注入式定子接地保护的研究与开发[C]//第十一届全国保护和控制学术研讨会论文集.2007.
- 谢小荣,韩英铎,电力系统频率测量综述[J].电力系统自动化,1999,3(3):1-10.
- 胡志坚,张承学.滤除衰减非周期分量的微机保护算法研究[J].电网技术,2001,25(3):7-11.