采用差绝缘方式降低110kV同塔双回线同跳几率Reduction of Simultaneous Trip Probability for 110 kV Double Circuit Transmission Lines on Same Tower by Unbalanced Insulation
陶礼兵,李志军
TAO Li-bing1,LI Zhi-jun2(1.Quzhou Electric Power Bureau
摘要(Abstract):
同塔双回输电线路若发生雷击,由于两回线路耐雷水平相当,较易发生同时闪络跳闸事故。为减少输电线路同时跳闸的概率,以某条110 kV输电线路为例,提出采用差绝缘的方法,降低输电线路双回跳闸率,同时考察了不同因素对雷击跳闸率的影响。结果表明:采用一回绝缘强度不变,另一回增加3片绝缘子的差绝缘方式,可将双回跳闸率降低至总跳闸率的12%以下。同时,减小地面倾斜角和避雷线保护角、采取合理的相序排列、减小接地电阻值都可以在一定程度上减小雷击跳闸率。
When the double circuit transmission line on the same tower is hit by lightning strike,flashover trip accident might occur at the same time as the lightning withstanding levels of the two lines are equal.Taking a 110 kV transmission lines as an example,this paper presents an unbalanced insulation method to reduce the rate of simultaneous trip of double circuit transmission lines while considering the effects of different factors on the trip rate.The simulation results show that after using the method of adding three insulators to one line while another remains unchanged,the double circuit trip rate can be lowered to 12% and below of the total trip rate.Meanwhile,the lightning trip rate can be decreased to some extent by reducing the ground inclination angle and the protection angle of ground wire,using reasonable phase sequence arrangement and reducing the grounding resistance.
关键词(KeyWords):
双回线路;差绝缘;耐雷水平;反击跳闸率
double circuit transmission line;unbalanced insulation;lightning withstanding level;back-flashover trip rate
基金项目(Foundation):
作者(Author):
陶礼兵,李志军
TAO Li-bing1,LI Zhi-jun2(1.Quzhou Electric Power Bureau
DOI: 10.19585/j.zjdl.2012.09.013
参考文献(References):
- 邹振盛.对110 kV同塔双回输电线路采用不平衡绝缘降低线路同时跳闸概率的研究[J].广东科技,2010(14):102-103.
- 黄培专.采用不平衡绝缘方式提高同塔双回线路供电可靠性[J].广东电力,2004,17(1):67-69.
- 解广润.电力系统过电压[M].北京:水利电力出版社,1985.
- DL/T 620交流电气装置过电压保护和绝缘配合[S].北京:中国电力出版社,1997.
- 吴玉麟,高建勇.高压输电线路绕击跳闸率的计算[J].四川电力技术,2008,31(3):16-18.
- 郑家松,李广福,季征南,等.山区500 kV输电线路雷电屏蔽性能模型试验研究[J].高压电器,2009,45(5):119-122.
- 双回线路
- 差绝缘
- 耐雷水平
- 反击跳闸率
double circuit transmission line - unbalanced insulation
- lightning withstanding level
- back-flashover trip rate