220kV断路器油泵电动机频繁启动的原因分析与处理Cause Analysis and Solution to Frequent Oil Pump Motor Start of 220 kV Circuit Breaker
潘中伟,肖驰夫,刘斌,苏强
PAN Zhongwei,XIAO Chifu,LIU Bin,SU Qiang
摘要(Abstract):
针对220 kV断路器油泵电动机频繁启动的问题,通过分析微动开关动作与油压升降的关系及油泵启停回路原理,找出了导致问题的原因为微动开关行程过长。根据分析结果调整了相应微动开关的行程,处理后问题得以消除,油泵电动机频繁启动现象再未出现。
The oil pump motor of 220 kV circuit breaker started frequently. By analysis of the relationship between micro switch action and oil pressure change as well as the theory of oil pump startup and shutdown circuit, it is found that the problem is caused by overlong switch limit. According to the analysis, the switch limit is adjusted, by which the problem is eliminated and the frequent start of oil pump motor occurs no more.
关键词(KeyWords):
220 kV断路器;油泵电动机;频繁启动;微动开关
220 kV circuit breaker;oil pump motor;frequent start;micro switch
基金项目(Foundation):
作者(Author):
潘中伟,肖驰夫,刘斌,苏强
PAN Zhongwei,XIAO Chifu,LIU Bin,SU Qiang
DOI: 10.19585/j.zjdl.2017.02.009
参考文献(References):
- [1]韩一霈,张惠民.220 kV断路器液压操作机构频繁打压故障分析及处理[J].河南电力,2014(2):42-44.
- [2]陈媛,张绿洲,林匹,等.某500 kV变电站220 kV断路器频繁打压的分析与处理[J].电力与电工,2010,30(4):48-49.
- [3]杨衡新.220 kV断路器操作机构故障处理及原因分析[J].水电站机电技术,2006,29(3):43-44.
- [4]韩筱慧,闻飞翔,费宇,等.HMB-4型液压弹簧操作机构频繁打压故障的现场检修[J].浙江电力,2015,34(4):69-72.
- [5]王彪,周程肖.FX22型断路器液压机构频繁启动原因分析[J].浙江电力,2011,30(6):17-18.