浙江电力

2016, v.35;No.246(10) 32-35

[打印本页] [关闭]
本期目录(Current Issue) | 过刊浏览(Archive) | 高级检索(Advanced Search)

基于特高频法的1100kV GIS局部放电缺陷定位研究
Application of UHF Method on Partial Discharge Detection in GIS

杨勇,王泓学,吴胥阳,王绍安,张静
YANG Yong,WANG Hongxue,WU Xuyang,WANG Shaoan,ZHANG Jing

摘要(Abstract):

针对一起1 100 kV GIS带电检测案例,阐述了GIS特高频局部放电检测原理和技术优势,分析了便携式局放仪的谱图信息,初步确定缺陷类型,并通过时差定位法对放电源进行了精确定位,查看1 100 kV GIS局部放电在线监测装置,模式识别技术的结果与现场判断一致,验证了现场带电检测的准确性。现场实践表明:特高频局部放电检测技术能有效识别GIS设备缺陷导致的局部放电,及时发现和避免GIS绝缘故障的发生,保障GIS设备的安全稳定运行。
According to a live detection of 1 100 kV GIS, this paper describes the principles and technical advantages of UHF-based GIS partial discharge detection method; in addition, it analyzes the spectrogram information of portable PD analyzer to preliminarily judge the defect type. At last, the discharge source is pre cisely located by means of time difference location method. The result of pattern recognition techniques of 1100 kV GIS partial discharge on-line monitoring system is consistent with the field test, which verifies the accuracy of the on-site live detection. Practice shows that UHF partial discharge detection technique can recognize partial discharge due to GIS defects, and timely discover and prevent GIS insulation faults to ensure the operation security and stability of GIS.

关键词(KeyWords): 特高频;GIS;局部放电;带电检测
UHF;GIS;partial discharge;live detection

Abstract:

Keywords:

基金项目(Foundation):

作者(Author): 杨勇,王泓学,吴胥阳,王绍安,张静
YANG Yong,WANG Hongxue,WU Xuyang,WANG Shaoan,ZHANG Jing

DOI: 10.19585/j.zjdl.2016.10.006

扩展功能
本文信息
服务与反馈
本文关键词相关文章
本文作者相关文章
中国知网
分享