基于特高频法的1100kV GIS局部放电缺陷定位研究Application of UHF Method on Partial Discharge Detection in GIS
杨勇,王泓学,吴胥阳,王绍安,张静
YANG Yong,WANG Hongxue,WU Xuyang,WANG Shaoan,ZHANG Jing
摘要(Abstract):
针对一起1 100 kV GIS带电检测案例,阐述了GIS特高频局部放电检测原理和技术优势,分析了便携式局放仪的谱图信息,初步确定缺陷类型,并通过时差定位法对放电源进行了精确定位,查看1 100 kV GIS局部放电在线监测装置,模式识别技术的结果与现场判断一致,验证了现场带电检测的准确性。现场实践表明:特高频局部放电检测技术能有效识别GIS设备缺陷导致的局部放电,及时发现和避免GIS绝缘故障的发生,保障GIS设备的安全稳定运行。
According to a live detection of 1 100 kV GIS, this paper describes the principles and technical advantages of UHF-based GIS partial discharge detection method; in addition, it analyzes the spectrogram information of portable PD analyzer to preliminarily judge the defect type. At last, the discharge source is pre cisely located by means of time difference location method. The result of pattern recognition techniques of 1100 kV GIS partial discharge on-line monitoring system is consistent with the field test, which verifies the accuracy of the on-site live detection. Practice shows that UHF partial discharge detection technique can recognize partial discharge due to GIS defects, and timely discover and prevent GIS insulation faults to ensure the operation security and stability of GIS.
关键词(KeyWords):
特高频;GIS;局部放电;带电检测
UHF;GIS;partial discharge;live detection
基金项目(Foundation):
作者(Author):
杨勇,王泓学,吴胥阳,王绍安,张静
YANG Yong,WANG Hongxue,WU Xuyang,WANG Shaoan,ZHANG Jing
DOI: 10.19585/j.zjdl.2016.10.006
参考文献(References):
- [1]廖天明,郑传宝,陆如,等.应用特高频检测方法处理GIS局部放电故障[J].华东电力,2011(4):652-654.
- [2]李晓峰,刘振,庞先海,等.特高频局部放电检测技术在GIS设备上的典型应用[J].高压电器,2013(7):100-103.
- [3]陈贤熙,王俊波,余红波,等.移动式特高频在线监测系统在GIS局部放电检测中的应用[J].高压电器,2015,(5):157-161.
- [4]刘君华,姚明,黄成军,等.采用声电联合法的GIS局部放电定位试验研究[J].高电压技术,2009(10):2458-2463.
- [5]王文浩,胡锡幸,郦于杰,等.基于特高频法的1 100 k VGIS局部放电故障定位研究[J].浙江电力,2015,34(4):11-14.
- [6]王伟平,何炳锋.基于特高频法GIS局部放电在线检测技术的分析与应用[J].高压电器,2015(4):183-187.
- [7]覃剑,王昌长,邵伟民.特高频在电力设备局部放电在线监测中的应用[J].电网技术,1997(6):33-36.
- [8]高文胜,丁登伟,刘卫东,等.采用特高频检测技术的局部放电源定位方法[J].高电压技术,2009(11):2680-2684.
- [9]丁登伟,高文胜,刘卫东.采用特高频法的GIS典型缺陷特性分析[J].高电压技术,2011(3):706-710.