“交改直”±200 kV同塔三回直流线路过电压研究Study on overvoltage in ±200 kV triple-circuit DC transmission lines on the same tower for an AC-to-DC transmission project
陈松涛,陈兵,吴巍,柏彬,赵会龙,廖黎明,杨庆
CHEN Songtao,CHEN Bing,WU Wei,BAI Bin,ZHAO Huilong,LIAO Liming,YANG Qing
摘要(Abstract):
在同塔双回交流输电的设施基础上将其改造为同塔三回直流输电,无需大规模新增投资、消耗输电走廊资源便能显著提高输电容量。针对同塔三回直流线路的绝缘配合设计,依托国内首个交流改直流±200 kV扬州—镇江直流输电工程,对6种直流极线布置方案下过电压沿直流线路的分布特性和最大电压进行比较分析,并与单回架设直流线路的过电压进行对比。此外,分析了影响同塔架设三回直流线路过电压水平的因素。研究表明,同塔三回直流线路不同布置方式下线路过电压的沿线分布特性相近,且同塔三回架设线路过电压水平略低于单回架设线路;直流系统输送功率大小、直流滤波器主电容与土壤电阻率是影响过电压水平的主要因素。研究结果已为扬州—镇江直流工程的设计建造提供了技术依据。
Converting double-circuit AC transmission lines on the same tower to triple-circuit DC transmission lines can significantly enhance transmission capacity without requiring large-scale additional investments or consuming transmission corridor resources. Focusing on the insulation coordination design of triple-circuit DC lines on the same tower, this paper examines the ±200 kV Yangzhou-Zhenjiang AC-to-DC transmission project, the first of its kind in China. Six DC pole line layout schemes are analyzed to compare the distribution characteristics and maximum overvoltage along the DC lines, with results further compared to single-circuit DC line configurations. Additionally, the factors influencing overvoltage levels in triple-circuit DC lines on the same tower are explored. The findings indicate that the overvoltage distribution characteristics along the line are similar across different layout schemes for triplecircuit lines, and the overvoltage levels for triple-circuit lines on the same tower are slightly lower than those of single-circuit lines. Key influencing factors include the DC system's transmission power, the main capacitance of DC filters, and soil resistivity. These results have provided a technical foundation for the design and construction of the Yangzhou-Zhenjiang AC-to-DC transmission project.
关键词(KeyWords):
交流改直流输电;高压直流输电;同塔三回线路;线路过电压
AC-to-DC transmission;HVDC transmission;triple-circuit transmission lines on the same tower;line overvoltage
基金项目(Foundation): 国家自然科学基金(52077019)
作者(Author):
陈松涛,陈兵,吴巍,柏彬,赵会龙,廖黎明,杨庆
CHEN Songtao,CHEN Bing,WU Wei,BAI Bin,ZHAO Huilong,LIAO Liming,YANG Qing
DOI: 10.19585/j.zjdl.202503012
参考文献(References):
- [1]张添胤,王启隆,王新,等.不同直流拓扑结构和敷设环境下35 kV交流XLPE电缆直流载流量分析[J/OL].西南交通大学学报:1-9[2024-06-05]. http://kns. cnki. net/kcms/detail/51.1277.U.20230505.1625.012.html.ZHANG Tianyin,WANG Qilong,WANG Xin,et al.Analysis of DC current carrying capacity of 35 kV AC XLPE cables under different DC topologies and laying environments[J/OL].Journal of Southwest Jiaotong University:1-9[2024-06-05]. http://kns. cnki. net/kcms/detail/51.1277.U.20230505.1625.012.html.
- [2]丁玉剑,廖蔚明,宿志一,等.±800 kV同塔双回直流线路杆塔空气间隙的放电特性影响因素研究[J].中国电机工程学报,2014,34(18):2983-2989.DING Yujian,LIAO Weiming,SU Zhiyi,et al.Research on the influence factors of discharge characteristics of air gaps for±800 kV double line transmission towers[J].Proceedings of the CSEE,2014,34(18):2983-2989.
- [3]朱艺颖,呙虎,孙栩,等.单回800 kV直流线路与双回500 kV交流线路同塔架设的电磁暂态仿真研究[J].电网技术,2012,36(11):217-221.ZHU Yiying,GUO Hu,SUN Xu,et al.Simulation study on electromagnetic transient of single circuit±800 kV DC transmission line and double circuit of 500kV AC transmission lines erected on same tower[J].Power System Technology,2012,36(11):217-221.
- [4]李鹏,李金忠,崔博源,等.特高压交流输变电装备最新技术发展[J].高电压技术,2016,42(4):1068-1078.LI Peng,LI Jinzhong,CUI Boyuan,et al.Achievements in the newest technology of UHV AC power transmission equipment[J]. High Voltage Engineering,2016,42(4):1068-1078.
- [5]舒印彪,张文亮.特高压输电若干关键技术研究[J].中国电机工程学报,2007,27(31):1-6.SHU Yinbiao,ZHANG Wenliang. Research of key technologies for UHV transmission[J]. Proceedings of the CSEE,2007,27(31):1-6.
- [6]董鹏,朱艺颖,习工伟,等.特高压直流输电线路内过电压仿真及机理分析[J].电网技术,2017,41(4):1114-1123.DONG Peng,ZHU Yiying,XI Gongwei,et al.Simulation and mechanism analysis of internal overvoltage of UHVDC transmission lines[J]. Power System Technology,2017,41(4):1114-1123.
- [7]朱艺颖,刘翀,王薇薇,等.同塔双回特高压直流线路过电压研究[J].电网技术,2013,37(8):2225-2229.ZHU Yiying,LIU Chong,WANG Weiwei,et al.Study on overvoltage in UHVDC double-circuit transmission lines on same tower[J]. Power System Technology,2013,37(8):2225-2229.
- [8]周浩,李济沅,王东举,等.±800 kV特高压直流输电线路单极接地故障过电压产生机理及影响因素[J].电力自动化设备,2016,36(4):1-6.ZHOU Hao,LI Jiyuan,WANG Dongju,et al.Overvoltage generation mechanism during single-pole grounding fault of±800 kV UHVDC transmission lines and its influencing factors[J]. Electric Power Automation Equipment,2016,36(4):1-6.
- [9]吴维韩,张芳榴.电力系统过电压数值计算[M].北京:科学出版社,1989:35-50.
- [10]张纬钹,何金良,高玉明.过电压防护及绝缘配合[M].北京:清华大学出版社,2002:24-46.
- [11]鲁俊,吕金锋,田蔚光,等.±500 kV柔性直流同塔三回架空导线布置方式[J].南方电网技术,2019,13(12):47-52.LU Jun,LüJinfeng,TIAN Weiguang,et al.Conductors arrangement of±500 kV VSC-DC overhead line with three circuits on the same tower[J].Southern Power System Technology,2019,13(12):47-52.
- [12]陈锡磊,周浩,王东举,等.800 kV浙西特高压直流换流站暂态过电压研究[J].电网技术,2012,36(3):22-27.CHEN Xilei,ZHOU Hao,WANG Dongju,et al.Study on transient overvoltage of Zhexi converter station of±800kV DC power transmission project[J]. Power System Technology,2012,36(3):22-27.
- [13]汪凤娇.高压/特高压直流输电系统操作过电压特性研究[D].广州:华南理工大学,2015.WANG Fengjiao.Study on operating overvoltage characteristics of HVDC and UHVDC transmission system[D].Guangzhou:South China University of Technology,2015.
- [14]朱艺颖,呙虎,李新年,等.锦屏—苏南特高压直流输电工程直流线路电磁暂态仿真[J].电网技术,2009,33(6):1-4.ZHU Yiying,GUO Hu,LI Xinnian,et al. Simulation on electromagnetic transient process in DC transmission line of±800 kV power transmission project from Jinping to South Jiangsu[J]. Power System Technology,2009,33(6):1-4.
- [15]周全,别睿,涂莉,等.±800 kV直流线路故障过程中电磁耦合特性与保护研究[J].电网技术,2014,38(8):2133-2140.ZHOU Quan,BIE Rui,TU Li,et al.Research on electromagnetic coupling characteristics during fault process in±800 kV UHVDC transmission line and its protection strategy[J]. Power System Technology,2014,38(8):2133-2140.
- [16]苏宜靖,张光明,于竞哲,等.直流滤波器对±800 kV直流线路单极接地故障过电压的影响[J].能源工程,2017(2):19-24.SU Yijing,ZHANG Guangming,YU Jingzhe,et al.Influence of DC filter parameters on single-pole grounding faultovervoltage in±800 k V UHVDC transmission line[J].Energy Engineering,2017(2):19-24.
- [17]徐鑫森,徐习东,陈金玉,等.考虑三次谐波调制的柔直系统交流侧单相接地保护研究[J].浙江电力,2024,43(10):114-123.XU Xinsen,XU Xidong,CHEN Jinyu,et al.Research on single-phase grounding fault protection on the AC side of VSC-HVDC systems considering third harmonic modulation[J].Zhejiang Electric Power,2024,43(10):114-123.
- [18]唐俊,赵文强,姜崇学,等.混合级联特高压直流输电系统逆变站保护功能及闭锁策略设计[J].浙江电力,2024,43(10):103-113.TANG Jun,ZHAO Wenqiang,JIANG Chongxue,et al.Design of protection functions and block strategies for inverter station of a hybrid cascaded UHVDC transmission system[J]. Zhejiang Electric Power,2024,43(10):103-113.
- [19]程骁,顾乔根,任旭超,等.海上风电柔性直流输电换流变差动保护的适应性分析[J].浙江电力,2024,43(3):8-18.CHENG Xiao,GU Qiaogen,REN Xuchao,et al. Adaptability analysis on differential protection of converter transformers in a VSC-HVDC transmission system connected to offshore wind farms[J].Zhejiang Electric Power,2024,43(3):8-18.
- 交流改直流输电
- 高压直流输电
- 同塔三回线路
- 线路过电压
AC-to-DC transmission - HVDC transmission
- triple-circuit transmission lines on the same tower
- line overvoltage