220kV闸刀支柱绝缘子断裂原因分析Analysis of 220 kV Switch Post Insulator Breakdown Accident
叶自强
YE Zi-qiang(Zhejiang Electric Power Test and Research Institute
摘要(Abstract):
针对220kV闸刀支柱绝缘子发生断裂的原因及机理进行了分析,指出绝缘子瓷质劣化及操作时冲击应力作用是断裂的二大原因。为防止同类事故的再次发生,提出对类似支柱绝缘子仍需运行的应经超声波探伤检测的观点。
220 kV switch post insulator breakdown accident in Lishui Substation is introduced. The post insulator breakdown mechanism is analyzed. To prevent similar accident, ultrasonic inspection is recommended.
关键词(KeyWords):
支柱绝缘子;断裂;原因;分析
post insulator; breakdown; reason; analysis