浙江电力

2013, v.32;No.212(12) 1-5+37

[打印本页] [关闭]
本期目录(Current Issue) | 过刊浏览(Archive) | 高级检索(Advanced Search)

35kV直挂链式静止同步补偿器的现场试验
Field Test of 35 kV Chain Type Hanging Static Synchronous Compensator

蔡重凯,王敏,陈晓宇,李电,刘文华
CAI Chongkai,WANG Min,CHEN Xiaoyu,LI Dian,LIU Wenhua

摘要(Abstract):

介绍35 kV电压等级直挂链式静止同步补偿器(STATCOM)在浙江220 kV变电站的应用概况,对装置进行了现场试验,包括上电前试验、恒无功试验、电压无功综合控制试验和电压暂态跌落试验等,测试结果符合装置的性能指标要求,试验方法可供相关单位进行STATCOM调试及验收试验参考。
This paper introduces application of 35 kV chain type hanging static synchronous compensator(STATCOM) in 220 kV substation in Zhejiang. A filed test is conducted on the device, including pre-charging test, constant reactive power test, synthetic control of voltage and reactive power and transient voltage sag. The test result is in conformity with the requirement of performance index, and the test method can provide relevant units with reference for STATCOM commissioning and acceptance tests.

关键词(KeyWords): STATCOM;静止同步补偿器;35 kV;直挂;现场试验
STATCOM;static synchronous compensator;35 kV;hanging;field test

Abstract:

Keywords:

基金项目(Foundation):

作者(Author): 蔡重凯,王敏,陈晓宇,李电,刘文华
CAI Chongkai,WANG Min,CHEN Xiaoyu,LI Dian,LIU Wenhua

DOI: 10.19585/j.zjdl.2013.12.001

扩展功能
本文信息
服务与反馈
本文关键词相关文章
本文作者相关文章
中国知网
分享