油色谱在线监测装置是大型充油设备早期异常预警的有效手段,目前在110 kV及以上变压器上得到了广泛应用。通过对一起500 kV变压器轻瓦斯告警事件中变压器本体及油色谱装置进行原理分析、试验排查和模拟复现等,锁定缺陷原因为油色谱在线监测装置因程序错误,在油循环过程中产生气泡,长期运行过程中不断向变压器本体注入空气,当油中气体饱和后溢出至气体继电器,最终导致轻瓦斯告警。对该类缺陷原因进行深入分析,给出了相应运维建议:油色谱在线监测厂家要增加逻辑闭锁,确保不发生异常产气;运维单位应加强入网检测、装置校验并定期开展主变压器油中含气量测试,防止由于油中含气量一直上升,最终引发变压器轻瓦斯告警。
Online oil chromatography monitoring devices can be used for early warning of abnormalities in large oilfilled equipment. Therefore, they are now widely used in 110 kV and above transformers. Through principle analysis, test investigation, and simulation reproduction of the transformer body and the oil chromatography monitoring device in a light gas alarm of a 500 kV transformer, the reason of the defect is cleared up: the online oil chromatography monitoring device generates bubbles in the process of oil circulation due to a program error. The air is continuously injected into the transformer body during long-term operation and overflows to the gas relay when the oil is saturated, eventually leading to a light gas alarm. The causes of such defects are thoroughly analyzed, and corresponding suggestions on operation and maintenance are offered: the manufacturer of the online oil chromatography monitoring device should design a logic blocking to ensure that no abnormal gas generates; the operation and maintenance department should step up admittance testing, device calibration and regularly test the content of the air in the oil.
关键词(KeyWords):
油色谱在线监测;变压器;轻瓦斯告警;含气量
online oil chromatography monitoring;transformer;light gas alarm;air content
基金项目(Foundation): 国网江苏省电力有限公司科技项目(J2020135)
作者(Author):
张正东,宋博,甘强
ZHANG Zhengdong,SONG Bo,GAN Qiang
DOI: 10.19585/j.zjdl.202305014
参考文献(References):
- [1]年泓昌.500 kV变压器绝缘油含气量超标分析与处理[J].电工电气,2020(7):44-46.NIAN Hongchang.Analysis and treatment of overstandard gas content in insulation oil of 500 kV transformer[J].Electrotechnics Electric(Jiangsu Electrical Apparatus),2020(7):44-46.
- [2]王乾,杨立新.变压器油电气性能的影响因素分析[J].电力建设,2008,29(8):61-65.WANG Qian,YANG Lixin. Analysis of factors affecting transformer oil electric performances[J]. Electric Power Construction,2008,29(8):61-65.
- [3] XU Peng,CHU Zhoujian,SEHNG Zhilei,et al.Analysis and treatment of an abnormal insulation phenomenon of1 000 kV high voltage reactor iron core and clamp[J].Transform,2020,57(4):65-68.
- [4]刁磊,高鹏飞,魏建云.探究影响变压器油电气性能的因素[J].科学家,2016,4(6):201.DIAO Lei,GAO Pengfei,WEI Jianyun.Explore the factors affecting the electrical properties of transformer oil[J].Technology and Life,2016,4(6):201.
- [5]杨志,毛伟强,智慧,等.主变压器油含气量超标原因分析及处理[J].山东工业技术,2017(22):28.YANG Zhi,MAO Weiqiang,ZHI Hui,et al.Cause analysis and treatment of excessive gas content in main transformer oil[J]. Shandong Industrial Technology,2017(22):28.
- [6]刘浩军,蔺家骏,郑一鸣,等.一起交流特高压电抗器套管的油中溶解气体异常分析[J].浙江电力,2020,39(12):129-134.LIU Haojun,LIN Jiajun,ZHENG Yiming,et al.Abnormal analysis of dissolved gas in oil of AC UHV reactor bushing[J].Zhejiang Electric Power,2020,39(12):129-134.
- [7]李逊,徐浩俊.一起变压器油色谱异常的分析及处理[J].浙江电力,2010,29(5):28-30.LI Xun,XU Haojun.Analysis on the chromatogram abnormity of the auxiliary transformer oil[J].Zhejiang Electric Power,2010,29(5):28-30.
- [8] LI Guodong,YU Hua,LIU Hong,et al.Turn to turn insulation diagnosis of dry air core reactor[J]. Transformer,2019,56(12):13-18.
- [9]国家能源局.变压器油中溶解气体分析和判断导则:DL/T 722—2014[S].北京:中国电力出版社,2015.
- [10]国家质量监督检验检疫总局,中国国家标准化管理委员会.运行变压器油维护管理导则:GB/T 14542—2005[S].北京:中国标准出版社,2005.
- [11]何宁辉,丁立,沙伟燕,等.变压器油色谱在线监测装置性能检测系统设计[J].现代科学仪器,2022,39(3):16-20.HE Ninghui,DING Li,SHA Weiyan,et al.Design of performance detection system for transformer oil chromatographic online monitoring device[J].Modern Scientific Instruments,2022,39(3):16-20.
- [12]梁华.电力变压器油色谱在线监测装置的应用及装置故障分析[J].电子测试,2021(7):118-119.LIANG Hua. Application and fault analysis of on line monitoring device for power transformer oil chromatogram[J].Electronic Test,2021(7):118-119.
- [13]蒋超.变压器油色谱在线监测装置的应用与运维管理[J].电力系统装备,2020(14):107-108.JIANG Chao. Analysis on the application and operation and maintenance management of transformer oil chromatography online monitoring device[J].Electric Power System Equipment,2020(14):107-108.
- [14] LI Hao,YAN Nianping,JIA Zhidong.Study on the influence of moisture on insulation of dry type air core reactor[J].High Voltage Apparatus,2020,56(5):55-61.
- [15] ZHENG Zongan. Research and application of detection method of short circuit between turns of reactor based on magnetic field detection[J]. High Voltage Apparatus,2020,56(3):217-223.
- [16] HU Han,LIU Xu,JI Jie,et al.Diagnosis and analysis of a500 kV high reactance factory discharge fault[J]. Transformer,2020,57(4):69-73.