交流特高压变电站无功补偿设备电压等级高、容量大、投切频繁,对投切开关要求较高,综合可靠性和安全性考虑,浙江某交流特高压变电站采用带选相分合闸装置的SF_6开关,能有效降低无功设备投切时的操作过电压和合闸涌流,减小对系统及无功设备的冲击,延长开关的机械寿命,同时能规避负荷开关的不足。针对选相分合闸装置在安装、调试、运维阶段出现的误接线、误发"事故总"信号、功能开关切换错误等问题进行了分析,并给出处理建议。
Characterized by high voltage level, large capacity and frequent switching, reactive power equipment in the UHV AC substation has stringent requirement on switches. In consideration of reliability and safety, SF_6 switch with phase selection device is used in the UHV AC station in Zhejiang to reduce switching overvoltage and reclosing surge current of the reactive power device during its operation and decrease the impact on system and reactive power device to prolong mechanical durability and avoid the disadvantages of load switch. The paper analyzes wrong wiring, "integrated accident" signaling and wrong operation of function switches during phase selection device installation, commissioning as well as operation and maintenance; besides, it presents some recommendations.
关键词(KeyWords):
选相分合闸;交流特高压;无功补偿;处理建议
phase selection;UHV AC;reactive compensation;recommendations
基金项目(Foundation):
作者(Author):
李显鹏,刘世安,程兴民,姜涛
LI Xianpeng,LIU Shian,CHENG Xingmin,JIANG Tao
DOI: 10.19585/j.zjdl.2016.12.011
参考文献(References):
- [1]林立生.切合电容器组用断路器的选择[J].河北电力技术,1989(3):47-50.
- [2]周鼎.关于选相合闸的思考[J].高压电器,1996(6):33-34.
- [3]杨广羽,李锋涛,刘高峰,等.高压直流输电工程跳合闸选相装置的工作原理及应用[J].电力系统保护与控制,2010,38(16):108-110.
- [4]颜湘莲,李志兵.1 000 k V淮南---上海特高压交流输电示范工程系统调试110 k V侧断路器选相功能测试方案[R].北京:中国电力科学研究院,2013.
- [5]颜湘莲,刘北阳,王浩.1 000 k V淮南---上海特高压交流输电示范工程系统调试110 k V侧断路器选相功能测试[R].北京:中国电力科学研究院,2013.
- [6]王磊.合闸角控制装置Switchsync F236的安装和调试[J].高电压技术,2008,34(7):1525-1527.