基于污闪电压的自然积污绝缘子外绝缘状态评价External Insulation Condition Evaluation of Naturally Polluted Insulators Based on Pollution Flashover Voltage
胡文堂,王少华,姜文东,吴尊东
HU Wentang,WANG Shaohua,JIANG Wendong,WU Zundong
摘要(Abstract):
以浙江电网挂网运行的不同结构型式自然积污绝缘子为研究对象,在人工雾室进行污闪试验得到其污闪电压,并对其外绝缘状态进行评价,分析各种型式自然积污绝缘子的污秽度安全区域。结果表明:部分取样自然积污绝缘子的绝缘裕度较低,应及时采取防污闪措施。绝缘子上、下表面的污秽分布越不均匀,污秽不均匀度K值越小,绝缘子安全运行的允许ESDD值越大。总体上,钟罩型绝缘子的污秽度安全区域最大,双伞型绝缘子次之,普通型绝缘子的安全区域最小。
Taking different types of naturally polluted insulators on overhead transmission lines in Zhejiang power grid as research objects, pollution flashover tests were conducted in the artificial fog chamber and the pollution flashover voltage was obtained. On this basis, the external insulation condition was evaluated. The contamination safety zone of naturally polluted insulators was analyzed. The results show that the insulation margin of some sampled naturally polluted insulators was very low. It is necessary to take some timely measures for prevention from pollution flashover. The unevener the pollution distribution of upper and lower surfaces of polluted insulators is, the smaller the unevenness degree is, the larger the allowed equivalent salt deposit density(ESDD) value for safe operation is. On the whole, the safety zone of bell jar insulators is the largest, followed by the double-shed insulators and the safety zone of the common type insulators is the smallest.
关键词(KeyWords):
绝缘子;自然污秽;输电线路;污闪电压;状态评价;安全区域
insulator;natural pollution;transmission line;pollution flashover voltage;condition evaluation;safety zone
基金项目(Foundation):
作者(Author):
胡文堂,王少华,姜文东,吴尊东
HU Wentang,WANG Shaohua,JIANG Wendong,WU Zundong
DOI: 10.19585/j.zjdl.2016.03.001
参考文献(References):
- [1]孙才新,司马文霞,舒立春.大气环境与电气外绝缘[M].北京:中国电力出版社,2002.
- [2]关志成.绝缘子及输变电设备外绝缘[M].北京:清华大学出版社,2006.
- [3]王向朋,周军,王黎明,等.高海拔下特高压直流绝缘子的污闪特性[J].高电压技术,2008,34(9):1869-1874.
- [4]范建斌,黄志秋,谢荣坤,等.直流输电线路Y型绝缘子串污闪特性研究[J].电网技术,2007,31(18):32-35.
- [5]关志成,龙彪,张福增,等.高海拔地区直流绝缘子不同悬挂方式污闪特性[J].高电压技术,2007,33(10):1-5.
- [6]胡建林,蒋兴良,张志劲,等.布置方式对直流绝缘子串人工污秽闪络特性的影响[J].电网技术,2006,30(23):15-18.
- [7]李震宇,崔吉峰,周远翔,等.绝缘子安装结构对污闪电压的影响[J].电网技术,2005,29(16):56-59.
- [8]JIANG XINGLIANG,WANG SHAOHUA,ZHANG ZHI-JIN,et al.Investigation of flashover voltage and non-uniform pollution correction coefficient of short samples of composite insulator intended for±800 k V UHVDC[J].IEEETrans on Dielectrics and Electrical Insulation,2010,17(1):71-80.
- [9]LAMPE W,H魻GLUND T,NELLIS C,et al.Long-term tests of HVDC insulators under natural pollution conditions at the Big Eddy Test Center[J].IEEE Trans on Power Delivery,1989,4(1):248-258.
- [10]TAKASU K,SHINDO T,ARAI N.Natural contamination test of insulators with DC voltage energization at inland areas[J].IEEE Trans on Power Delivery,1988,3(4):1847-1853.