一起500 kV复合绝缘子断裂故障分析Cause analysis on fracture of a 500 kV composite insulator
李勃铖,李稳,张稷,邓园,黄浩,刘钢,雷添
LI Bocheng,LI Wen,ZHANG Ji,DENG Yuan,HUANG Hao,LIU Gang,LEI Tian
摘要(Abstract):
针对一起禁飞区500 kV复合绝缘子断裂导致导线掉线事故,依据现行标准对故障绝缘子开展了外观检测、材料性能试验和电气试验。综合现场事故调查情况和检测分析结果发现,由于复合绝缘子芯棒玻璃纤维与硅橡胶护套界面存在缺陷,在挂网运行多年后绝缘子芯棒老化,加之受运行环境综合影响,加剧了芯棒内部纤维化和整体结构变性,最终导致绝缘子酥朽断裂,进而发生导线脱串掉线事故。最后,给出无人机禁飞区、弱信号等区段线路复合绝缘子的运维策略及防范措施,以避免此类事故再次发生,确保电网安全稳定运行。
In order to study the cause of wire falling accident caused by fracture of 500 kV composite insulator in the no-fly zone of a province, various inspections and tests were carried out on the accident insulator string according to the current standard. The results of comprehensive detection and analysis and on-site fault investigation show that due to the defects in the interface between the glass fiber and the silicone rubber sheath of the composite insulator rod, the rod of the insulator is aged after many years of operation. In addition, due to the comprehensive influence of the operating environment, the internal fibrosis and overall structural degeneration of the rod are aggravated, which eventually causes the insulator to break down and cause the wire to fall off. Finally, in order to avoid the recurrence of such accidents and ensure the safe and stable operation of the power grid, the operation and maintenance strategy of composite insulators is given for the lines under the jurisdiction of the UAV no-fly zone and weak signal zone.
关键词(KeyWords):
复合绝缘子;无人机禁飞区;界面缺陷;芯棒老化;酥朽断裂
composite insulator;UAV no-fly zone;interface defects;rod aging;decay fracture
基金项目(Foundation): 国网湖南省电力有限公司科技项目(5216AJ22000B)
作者(Author):
李勃铖,李稳,张稷,邓园,黄浩,刘钢,雷添
LI Bocheng,LI Wen,ZHANG Ji,DENG Yuan,HUANG Hao,LIU Gang,LEI Tian
DOI: 10.19585/j.zjdl.202309014
参考文献(References):
- [1]张志劲,姬雅晴,许军,等.复合绝缘子替代瓷绝缘子对500 kV输电线路悬垂绝缘子串风偏性能影响[J].电网技术,2022,46(5):2017-2024.ZHANG Zhijin,JI Yaqing,XU Jun,et al.Influence of composite insulator replacing porcelain insulator on wind deflection performance of suspension insulator string of 500kV transmission lines[J]. Power System Technology,2022,46(5):2017-2024.
- [2]卢明,高超,吴焱松,等.复合绝缘子脆性断裂与酥朽断裂差异性研究[J].高压电器,2022,58(6):17-23.LU Ming,GAO Chao,WU Yansong,et al.Study on difference between brittle fracture and decay-like fracture of composite insulator[J].High Voltage Apparatus,2022,58(6):17-23.
- [3]刘云鹏,李乐,张铭嘉,等.复合绝缘横担界面特性检测研究现状[J].电工技术学报,2020,35(2):408-424.LIU Yunpeng,LI Le,ZHANG Mingjia,et al. Research status of interface detection for composite cross-arm[J].Transactions of China Electrotechnical Society,2020,35(2):408-424.
- [4]王康,朱亚洲,周辛南,等.运行复合绝缘子界面问题分析[J].中国电力,2018,51(4):45-52.WANG Kang,ZHU Yazhou,ZHOU Xinnan,et al.Analysis on the interfacial issues of running composite insulators[J].Electric Power,2018,51(4):45-52.
- [5]卢明,高超,张世尧,等.复合绝缘子早期酥朽故障诊断及异常发热机理研究[J].电瓷避雷器,2022(2):205-212.LU Ming,GAO Chao,ZHANG Shiyao,et al.Early decaylike aging diagnosis and mechanism of abnormal temperature rise of composite insulators[J].Insulators and Surge Arresters,2022(2):205-212.
- [6]卢明,刘泽辉,高超,等.国内输电线路复合绝缘子典型故障情况调查及原因分析[J].电瓷避雷器,2022(4):214-220.LU Ming,LIU Zehui,GAO Chao,et al.Investigation on typical fault of composite insulator in domestic transmission lines[J]. Insulators and Surge Arresters,2022(4):214-220.
- [7]贾然,周超,刘辉,等.芯棒快速老化导致的500 kV输电线路复合绝缘子芯棒断裂故障分析[J].山东电力技术,2021,48(4):41-46.JIA Ran,ZHOU Chao,LIU Hui,et al.Analysis of a 500kV composite insulator fracture fault caused by rapid aging of rod materials[J]. Shandong Electric Power,2021,48(4):41-46.
- [8]邵颖彪,卢明,马德英,等.河南电网一起500 kV复合绝缘子断裂故障分析[J].电瓷避雷器,2016(1):34-39.SHAO Yingbiao,LU Ming,MA Deying,et al.Analysis of a fracture accident of 500 kV composite insulators occurred in Henan grid[J].Insulators and Surge Arresters,2016(1):34-39.
- [9]张柳,巢亚锋,王成,等.500 kV输电线路复合绝缘子断裂事故分析[J].湖南电力,2018,38(5):27-31.ZHANG Liu,CHAO Yafeng,WANG Cheng,et al.Analysis of fracture accident of composite insulator for 500 kV transmission line[J].Hunan Electric Power,2018,38(5):27-31.
- [10]巢亚锋,王成,黄福勇,等.中国输电线路复合绝缘子运行状况分析[J].高压电器,2015,51(8):119-124.CHAO Yafeng,WANG Cheng,HUANG Fuyong,et al.Assessment on operation state of composite insulators used on Chinese transmission lines[J].High Voltage Apparatus,2015,51(8):119-124.
- [11]国家质量监督检验检疫总局,中国国家标准化管理委员会.架空线路绝缘子标称电压高于1 000 V交流系统用悬垂和耐张复合绝缘子定义、试验方法及接收准则:GB/T 19519—2014[S].北京:中国标准出版社,2015.
- [12]中华人民共和国国家市场监督管理总局,中国国家标准化管理委员会.户内和户外用高压聚合物绝缘子一般定义、试验方法和接收准则:GB/T 22079—2019[S].北京:中国标准出版社,2019.
- [13]中华人民共和国国家质量监督检验检疫总局,中国国家标准化管理委员会.硫化橡胶或热塑性橡胶压入硬度试验方法第1部分:邵氏硬度计法(邵尔硬度):GB 531.1—2008[S].北京:中国标准出版社,2008.
- [14]王成,袁之康,丁立健,等.复合绝缘子芯棒湿热条件下劣化特性研究[J].高压电器,2022,58(2):25-32.WANG Cheng,YUAN Zhikang,DING Lijian,et al.Study on deterioration of core rod of composite insulator at hydrothermal condition[J]. High Voltage Apparatus,2022,58(2):25-32.
- [15]李如锋,李光,李祥,等.复合绝缘子酸液侵蚀的脆断研究[J].陕西电力,2012,40(9):69-71.LI Rufeng,LI Guang,LI Xiang,et al. Probe into brittle fracture of composite insulators caused by acid erosion[J].Shaanxi Electric Power,2012,40(9):69-71.
- [16]梁曦东,高岩峰.复合绝缘子酥朽断裂研究(一):酥朽断裂的主要特征、定义及判据[J].中国电机工程学报,2016,36(17):4778-4786.LIANG Xidong,GAO Yanfeng.Study on decay-like fracture of composite insulator:part I-the principal character,definition and criterion of decay-like fracture[J].Proceedings of the CSEE,2016,36(17):4778-4786.