摘要(Abstract):

针对目前电抗器需要进行内检才能确定放电点个数的问题,基于流体力学以及溶质扩散的相关理论,分析了电抗器内部绝缘油的流型特征,建立了不同位置局放后乙炔的运动轨迹及在线气相色谱信号的变化模型,提出了利用在线色谱数据判断局放点数目和位置的方法,并对实际案例进行了分析。结果表明,乙炔在油箱中的运动主要依赖于油箱中绝缘油的流动,呈现出多阶段的振动衰减变化模式,可以利用乙炔浓度曲线的峰值平台期个数和不同采样口间曲线峰值时间指纹判断局放点数目和位置,并在实际案例中得到了验证。
In order to avoid the number of partial discharge(PD) in shunt reactor must be determined by internal examination, the fluid flow characteristics of insulation oil in the reactor is analyzed based on the hydrodynamics and diffusion theory. The movement track of acetylene and variation model of on-line chromatogram with different PD positions are built in this paper. A new method to determine the PD number and position by employing the on-line chromatogram is proposed. Finally, a practical case is analyzed by using the proposed method. The results show that the acetylene movement is mainly determined by the flow of insulation oil in oil tank and it presents several variation modes with oscillation attenuation. The PD number can be diagnosed through the number of peak platform in acetylene variation curve, and the PD position can be deduced by comparing the peak time finger chromatogram of acetylene variation curve between different sampling ports. Finally, the proposed method is verified by the reality case.

关键词(KeyWords): 在线监测;并联电抗器;局部放电;乙炔
online-monitor;shunt reactor;partial discharge;acetylene

Abstract:

Keywords:

基金项目(Foundation):

作者(Author): 何毅帆
HE Yifan

DOI: 10.19585/j.zjdl.2015.09.003

参考文献(References):

扩展功能
本文信息
服务与反馈
本文关键词相关文章
本文作者相关文章
中国知网
分享