浙江电力

2020, v.39;No.287(03) 36-42

[打印本页] [关闭]
本期目录(Current Issue) | 过刊浏览(Archive) | 高级检索(Advanced Search)

考虑盲目攻击因子的电力SCADA系统安全脆弱性评估
Security Vulnerability Assessment of Power SCADA System Considering Blind Attack Factor

周飞,吴金城,郑东亚,董树锋
ZHOU Fei,WU Jincheng,ZHENG Dongya,DONG Shufeng

摘要(Abstract):

电力SCADA(数据采集与监控)系统在电网中发挥着重大作用,如果受到攻击会造成巨大的经济损失,因此需要对其进行安全性评估并采取防御性措施。首先,解析电网SCADA系统结构,建立其攻击树模型;然后,对每个叶子节点分别从设定的3个安全特征进行等级评定,通过评比和计算给这3个特征赋权,并解得每个叶子节点的激活概率;接着,考虑盲目攻击因子,求解模型中所有节点的激活概率;最后,得出系统脆弱性以及各叶子节点的脆弱性灵敏度,并根据脆弱性灵敏度对系统薄弱环节进行重点防护。算例分析结果验证了所提评估方法的有效性。
Power SCADA(supervisory control and data acquisition) system plays a major role in the power grid. Attack on the system may cause huge economic losses. Therefore, it is necessary to evaluate their safety and take defensive measures. This paper first analyzes the system structure of SCADA, establishes its attack tree model; then it grades each leaf node from the set three security features, and gives weights to these three features through evaluation and calculation to obtain the activation probability of each leaf node; besides, the blind attack factor is considered to obtain the attack success probability of all nodes in the model; finally, the system vulnerability and the vulnerability sensitivity of each leaf node are obtained, and the protection of the weakness of the system is defended according to the vulnerability sensitivity. The effectiveness of the evaluation method is illustrated by an example.

关键词(KeyWords): SCADA系统;安全特征;盲目攻击因子;脆弱性灵敏度
SCADA system;security feature;blind attack factor;vulnerability sensitivity

Abstract:

Keywords:

基金项目(Foundation): 国家自然科学基金资助(51677165);; 群众性创新研究(NB020XT06)

作者(Author): 周飞,吴金城,郑东亚,董树锋
ZHOU Fei,WU Jincheng,ZHENG Dongya,DONG Shufeng

DOI: 10.19585/j.zjdl.202003006

参考文献(References):

扩展功能
本文信息
服务与反馈
本文关键词相关文章
本文作者相关文章
中国知网
分享