特高压变电站高压电抗器地屏铜条断裂原因分析Cause Analysis on Copper Bars Fracture of a High-voltage Reactor Ground Screen of Ultra-high Voltage Substation
周宇通,王炯耿,张杰,胡洁梓,梅简
ZHOU Yutong,WANG Jionggeng,ZHANG Jie,HU Jiezi,MEI Jian
摘要(Abstract):
某特高压变电站1台高压电抗器地屏中的铜条异常断裂,导致设备停运。运用SEM和EDS等技术对铜条断裂原因进行了分析。结果表明:铜条断口表面不存在撕裂棱、韧窝等塑性断裂的典型特征;断口附近组织的平均晶粒尺寸明显大于远离断口的区域;粘附在铜条表面的黑色固态粘性物质为绝缘纸的高温碳化物。基于上述3点,可以判定铜条并非是机械振动拉断,而是由于局部过热熔断的。
Copper bars of a high-voltage reactor ground screen located in an ultra-high voltage substation fractured, resulting in equipment shutdown. SEM(scanning electron microscopy), EDS(energy dispersive X-ray spectrometer) and other techniques are adopted to analyze the reasons of copper bars fracture. The results indicate that no tearing ridge and dimple can be found on the surface of the fracture. The average grain size of the regions near the fracture is much larger than that of the regions far away from the fracture. The black solid sticky substance on copper bar surface is carbide of electrical insulating paper. Based on the above three points, it can be inferred that the copper bars are fused due to local overheating instead of mechanical vibration.
关键词(KeyWords):
特高压变电站;高压电抗器;铜条;断裂
ultra-high voltage substation;high-voltage reactor;copper bar;fracture
基金项目(Foundation):
作者(Author):
周宇通,王炯耿,张杰,胡洁梓,梅简
ZHOU Yutong,WANG Jionggeng,ZHANG Jie,HU Jiezi,MEI Jian
DOI: 10.19585/j.zjdl.2017.03.004
参考文献(References):
- [1]何毅帆.基于流体分析的并联电抗器局部放电的识别与定位研究[J].浙江电力,2015,34(9):10-14.
- [2]何文林,邵先军,赵寿生,等.面向对象的运行中变压器抗短路能力评估方法与应用研究[J].浙江电力,2016,35(7):1-7.
- [3]周勤勇,郭强,冯玉昌,等.可控高压电抗器在西北电网的应用研究[J].电网技术,2006,30(6):48-52.
- [4]林阳洋,宋克兴,国秀花.Al2O3/Cu复合材料的高温拉伸性能研究[J].铸造技术,2005,26(10):959-962.
- [5]张继东,李才巨,朱心昆,等.大塑性变形对纯铜力学性能的影响[J].云南冶金,2007,36(1):56-68.
- [6]赵品.材料科学基础教程[M].哈尔滨:哈尔滨工业大学出版社,2009.
- [7]王芸,安晓利,魏星,等.铜导线短路熔痕微观形貌特征分析与研究[J].火宅科学,2008,17(1):44-48.
- [8]杨晓红.火烧熔痕与短路熔痕形态特征差异研究[J].辽宁大学学报自然科学版,2014,41(3):230-234.
- [9]牛涛,汤金婷,李志军,等.木质纤维素原料预处理前后主要糖成分的测定[J].酿酒科技,2009,8:125-127.