1100kV GIS盆式绝缘子局部放电的现场带电检测与试验分析Experimental Analysis and On-site Live Partial Discharge Detection in 1 100 kV GIS Disk Insulator
邵先军,刘浩军,杜伟,杨勇,梅冰笑
SHAO Xianjun,LIU Haojun,DU Wei,YANG Yong,MEI Bingxiao
摘要(Abstract):
介绍一起1 100 kV GIS盆式绝缘子局部放电带电检测案例,重点阐述现场带电检测、在线监测跟踪、现场交流耐压下UHF检测以及返厂解体测试等过程的检测数据与分析,探讨分析了脉冲电流法与UHF法检测结果差异的可能原因。该案例有助于进一步理解UHF与脉冲电流法检测的差异性,并为基于带电检测的GIS状态评估技术提供现场数据参考。
An example of live partial discharge(PD) detection in disk insulator of 1 100 kV GIS is introduced.In this paper, the detection data and analysis of on-site live detection, online monitoring and track, UHF(ultra-high frequency) detection under AC withstanding voltage and plant disassembly test are presented. Besides, the possible reasons of detection result differences between pulse current method and UHF method are discussed and analyzed. The case is helpful to understand the difference between UHF and pulse current method, and it also provides an on-site reference for GIS condition assessment based on live detection.
关键词(KeyWords):
盆式绝缘子;局部放电;带电检测;在线监测
basin-type insulator;partial discharge;live detection;online monitoring
基金项目(Foundation):
作者(Author):
邵先军,刘浩军,杜伟,杨勇,梅冰笑
SHAO Xianjun,LIU Haojun,DU Wei,YANG Yong,MEI Bingxiao
DOI: 10.19585/j.zjdl.2016.10.005
参考文献(References):
- [1]陈小鑫,缪希仁.数字变电站监控系统与通讯技术[J].高压电器,2013,49(8):68-72.
- [2]侯伟宏,张沛超,胡炎.数字化变电站系统可靠性与可用性研究[J].电力系统保护与控制,2010(14):34-38.
- [3]高振兴,郭创新,俞斌,等.基于多信息融合的电网故障诊断方法研究[J].电力系统保护与控制,2011,39(6):17-22.
- [4]周立辉,张永生,孙勇,等.智能变电站巡检机器人研制与应用[J].电力系统自动化,2011,35(19):85-88.
- [5]杨森,董吉文,鲁守银.变电站设备巡检机器人视觉导航方法[J].电网技术,2009,33(5):11-16.
- [6]廖小君,黄忠胜,吕飞鹏.智能变电站监控与视频系统联动方式研究[J].四川电力技术,2014,37(5):42-45.
- [7]郭创新,彭明伟,刘毅.多数据信息融合的电网故障诊断新方法[J].中国电机工程学报,2009,29(31):1-7.
- [8]鲁守银,钱庆林,张斌,等.变电站设备巡检机器人的研制[J].电力系统自动化,2006,30(13):94-98.
- [9]王建元,王娴,陈永辉,等.基于图论的电力巡检机器人智能寻迹方案[J].电力系统自动化,2007,31(9):78-80.
- [10]赵书涛,李宝树,崔桂彦,等.基于计算机视觉的远程变电站状态监测与诊断新技术[J].电网技术,2005,29(6):63-66.