小电流接地系统单相接地故障选线方法研究Research on Single Phase-to-ground Fault Line Selection Methods in Small Current Grounding System
丁爱佳,鲍炫羽,季玲玲,江浩
DING Aijia,BAO Xuanyu,JI Lingling,JIANG Hao
摘要(Abstract):
对于小电流接地系统单相接地故障,现有选线装置在实际应用中效果并不理想,建议利用10k V变电站现有保护装置中的零序过流保护解决此问题。通过在10 k V中性点消弧线圈的基础上并联中电阻柜、对传统选线逻辑加以修改、对整定值进行修正,从而实现单相接地故障时,通过线路零序过流保护发信的先后顺序可靠选线,并给出验证实例。
The application of existing line selection device is not ideal for single phase-to-ground fault in small current grounding system. Therefore, the paper suggests using zero-sequence overcurrent protection in protective device of 10 k V substations to solve the problem. By parallel connection of neutral resistance cabinet with10 k V neutral arc suppression coil, correction of traditional line selection logic and settings modification, the fault line can be selected correctly in accordance to the messaging order of zero-sequence overcurrent protection of lines; in addition, the paper presents some verification cases.
关键词(KeyWords):
小电流接地;零序过流保护;选线逻辑
small current grounding;zero-sequence overcurrent protection;line selection logic
基金项目(Foundation):
作者(Author):
丁爱佳,鲍炫羽,季玲玲,江浩
DING Aijia,BAO Xuanyu,JI Lingling,JIANG Hao
DOI: 10.19585/j.zjdl.201705003
参考文献(References):
- [1]齐郑,杨以涵.中性点非有效接地系统单相接地选线技术分析[J].电力系统自动化,2004,28(14):1-5.
- [2]吴青军,黄驾驾,刘东红.零序过流保护在单相接地故障选线中的应用探讨[J].浙江电力,2016,35(5):47-49.
- [3]曹国臣,高宏慧.小电流接地系统两点异相接地故障计算的新方法[J].电网技术,2005,29(5):72-75.
- [4]单渊达.电能系统基础[M].北京:机械工业出版社,2001.
- [5]周戴明,王志亮,李康毅.小电流接地系统4TV接线极性判别方法[J].浙江电力,2016,35(1):27-30.
- [6]张婷娟,王涛,黄鹰.智能变电站小电流接地选线装置测试仪的研究与设计[J].东北电力大学学报,2016,36(1):13-17.
- [7]张耘川,苏宏升.小电流接地系统故障定位新方法[J].电力系统及其自动化学报,2015,27(2):32-38.