一起1100kV GIS盆式绝缘子击穿故障分析Analysis on Breakdown Failure in Basin-type Insulator of 1 100 kV GIS
刘石,蒋鹏,彭晨光,邵先军
LIU Shi,JIANG Peng,PENG Chenguang,SHAO Xianjun
摘要(Abstract):
介绍某特高压变电站一起1 100 kV GIS设备的盆式绝缘子内部击穿故障的发生过程,结合故障录波、SF6气体、局部放电在线监测结果确定了故障气室的位置,解体分析该气室盆式绝缘子内部击穿故障,讨论分析该故障可能的原因和发展过程,指出盆式绝缘子内部贯穿性放电是由产品在制造过程中内部存在空穴或异物缺陷导致的。
In this paper, an inner breakdown failure of basin-type insulator in GIS of an UHV substation is introduced briefly. By combing the fault recording, SF6 and online partial discharge monitoring, the faulty gas chamber is located accurately. By disassembly the inner breakdown fault of basin-type insulator in the gas chamber is analyzed, and the possible causes and degradation of this inner breakdown failure are analyzed. It is pointed out that the inner breakdown discharge is caused by cavities or foreign matters in the process of manufacture.
关键词(KeyWords):
特高压;GIS;盆式绝缘子;内部击穿
ultra-high voltage;GIS;basin-type insulator;inner breakdown
基金项目(Foundation):
作者(Author):
刘石,蒋鹏,彭晨光,邵先军
LIU Shi,JIANG Peng,PENG Chenguang,SHAO Xianjun
DOI: 10.19585/j.zjdl.2016.10.007
参考文献(References):
- [1]刘振亚.特高压交直流电网[M].北京:中国电力出版社,2014.
- [2]刘振亚.特高压交流输电技术研究成果专辑(2008年)[M].北京:中国电力出版社,2008.
- [3]陈允,于洋,崔博源,等.1 100 k V盆式绝缘子界面处理工艺及质量管控措施[J].绝缘材料,2015,48(5):44-49.
- [4]张宏建,李金玉,李仰平,等.环氧树脂浇注件中内部应力产生的形状因素和防止措施[J].绝缘材料通讯,1999(5):26-28.
- [5]许建春,卢鹏.1 100 k V GIS盆式绝缘子的性能[J].电力建设,2010,31(8):91-93.
- [6]李盛涛,郑晓泉.聚合物电树枝化[M].北京:机械工业出版社,2006.