浙江电力

2012, v.31;No.195(07) 24-26

[打印本页] [关闭]
本期目录(Current Issue) | 过刊浏览(Archive) | 高级检索(Advanced Search)

发电机出口TV断线异常跳机分析和处理
Analysis and Treatment of Abnormal Tripping for Generator Terminal TV Disconnection

吴梦可
WU Meng-ke(Zhejiang Energy Zhenhai Power Generation Co.

摘要(Abstract):

分析了发电机出口电压互感器(TV)断线引起励磁故障异常跳机的案例,指出主要原因是高压熔丝性能劣化,二次电压缓慢跌落,励磁调节器未能自动切换至备用通道所致,提出了切实可行的解决方案。
Through the analysis on the case of abnormal tripping for the excitation fault caused by the disconnection of generator terminal TV,this paper identifies the reason as high-voltage fuse performance degradation,slow drop of secondary voltage and excitation regulator failing to automatically switch to standby channel.In addition,it presents the feasible solution.

关键词(KeyWords): 励磁调节器;TV断线;跳机
excitation regulator;TV disconnection;tripping

Abstract:

Keywords:

基金项目(Foundation):

作者(Author): 吴梦可
WU Meng-ke(Zhejiang Energy Zhenhai Power Generation Co.

DOI: 10.19585/j.zjdl.2012.07.008