基于谐波特征的活体触电判据研究Research on Live Electric Shock Criterion Based on Harmonic Characteristics
潘永长,李紫莲,凌军,贺立,吕诚聪,姚文浩,赵阳
PAN Yongchang,LI Zilian,LING Jun,HE Li,LYU Chengcong,YAO Wenhao,ZHAO Yang
摘要(Abstract):
传统的剩余电流断路器仅以电流超过断路器动作电流整定值来判断故障,如果台区漏电流过大,很容易导致剩余电流断路器误动作。为此,提出将谐波变化率最小值阈值与断路器动作电流整定值相结合的判据,来判断线路是否发生触电。首先搭建活体触电实验平台,进行活体不同部位的触电实验;其次,应用快速傅里叶变换提取谐波特征,计算得到谐波变化率最小值的阈值区间;最后,通过人体触电仿真算例验证了活体触电实验的结论,证明了所提判据的可靠性。
For the traditional residual current circuit breaker, fault judgment relies merely on whether the current exceeds the setting value of the action current of circuit breaker. Circuit breaker misoperation of residual current may occur if there is strong residual leakage current in the transformer area. Therefore, the paper proposes a criterion that combines the minimum threshold value of harmonic change rate and action current setting value of circuit breaker is proposed to judge whether electric shock fault occurs in the circuit.Firstly, a live electric shock experiment platform is set up to carry out electric shock experiments in different parts. Secondly, the harmonic features are extracted by FFT transformation, and then the minimum threshold interval of the harmonic change rate is calculated. Finally, the conclusion of the live shock experiment is verified by the human shock simulation, and the reliability of the criterion is verified.
关键词(KeyWords):
快速傅里叶变换;触电实验;谐波特征;谐波变化率最小值;判据
FFT;electric shock test;harmonic characteristics;minimum value of harmonic change rate;criterion
基金项目(Foundation):
作者(Author):
潘永长,李紫莲,凌军,贺立,吕诚聪,姚文浩,赵阳
PAN Yongchang,LI Zilian,LING Jun,HE Li,LYU Chengcong,YAO Wenhao,ZHAO Yang
DOI: 10.19585/j.zjdl.202101009
参考文献(References):
- [1]高阁,李春兰,张亚飞,等.基于正交实验触电实验平台参数优化及触电信号分析[J].中国农机化学报,2019,40(9):181-188.
- [2]李奎,陆俭国,岳大为,等.漏电信号的识别技术及其方法[J].低压电器,2008(23):1-4.
- [3]夏兰兰,李春兰,王成斌,等.基于混沌系统功率谱特征的触电信号识别研究[J].华北电力技术,2017(9):1-7.
- [4]李春兰,夏兰兰,王成斌,等.基于椭圆域分割的触电电流混沌检测方法研究[J].电力系统保护与控制,2017,45(15):69-76.
- [5]李春兰,苏娟,杜松怀,等.基于小波分析和BP神经网络的触电信号检测模型[J].农业工程学报,2010,26(增刊2):130-134.
- [6]郭滨滨.快速傅里叶变换信号识别能力分析[J].现代电子技术,2007(7):58-60.
- [7]吴禹,唐求,滕召胜,等.基于改进S变换的电能质量扰动信号特征提取方法[J].中国电机工程学报,2016,36(10):2682-2689.
- [8]杨剑锋,姜爽,石戈戈.基于分段改进S变换的复合电能质量扰动识别[J].电力系统保护与控制,2019,47(9):64-71.
- [9]马杰,孙宁,任志强,等.基于多特征组合的电能质量扰动识别方法[J].电力电容器与无功补偿,2019,40(2):125-130.
- [10]舒成维,王承民,谢宁.一种基于坐标变换的剩余电流提取方法[J].电力系统保护与控制,2018,46(15):111-119.
- [11]赵彦,王俊江,卓梦飞,等.基于暂态方向的小电流接地故障多级保护技术[J].水电能源科学,2018,36(10):185-189.
- [12]王启立,詹宇飞,陈志强,等.接地阻抗变化量判据的触电漏电保护[J].电工技术,2017(6):15-17.
- [13]应晓云.漏电保护器动作特性分析[J].浙江电力,1996,15(1):43-45.
- [14]滕松林.信号分离动作型全自动触电漏电保护器[J].北京农业工程大学学报,1994(3):79-83.
- [15]谢善益,肖斐,艾芊,等.多域分布式数据库的电能质量扰动事件记录关联规则挖掘[J].电网与清洁能源,2020,36(5):35-41.
- [16]胡殿刚,马喜平,赵凤展,等.一种基于短时傅里叶变换的电压闪变信号的检测[J].电网与清洁能源,2020,36(3):27-33.
- [17]汪玉翔,梁伟萍.LEC法加入模糊影响图算法的变电站施工触电风险研究[J].电力大数据,2019,22(11):21-28.
- [18]黎学春,高宇男,李磊,等.基于自适应神经网络系统聚类的特殊负荷分类研究[J].电网与清洁能源,2019,35(1):8-15.
- 快速傅里叶变换
- 触电实验
- 谐波特征
- 谐波变化率最小值
- 判据
FFT - electric shock test
- harmonic characteristics
- minimum value of harmonic change rate
- criterion