变压器励磁涌流闭锁逻辑优化方案Excitation Inrush Current Blocking Logic Optimization Scheme of Transformer
周浩,石磊,吕强
ZHOU Hao,SHI Lei,LYU Qiang
摘要(Abstract):
变压器在空载合闸时会产生励磁涌流,由于空载合闸角、剩磁以及变压器结构材料和制造工艺的差异导致励磁涌流存在较大差异,可能存在低谐波比的情况,使得常规的励磁涌流判据可能无法有效闭锁差动保护。结合工程中空投变压器导致差动保护动作的案例,分析总结出特殊工况下励磁涌流的特征,在原励磁涌流逻辑基础上,提出采用"3取2"复合制动、相电流谐波判据和最大相谐波判据的综合制动逻辑,解决了工程中遇到的无法识别低谐波比励磁涌流的问题,最后通过仿真和工程实例验证了该优化方案的优越性。
The magnetizing inrush current is generated in the transformer no-load closing. The no-load closing angle, residual magnetism and differences in transformer structural materials and manufacturing processes lead to large differences of excitation inrush current. Therefore, conventional excitation inrush current criterion may not effectively block differential protection due to low harmonic ratio. In view of the cases of differential protection action caused by a no-load transformer in engineering practice, excitation inrush characteristics under special operation condition is analyzed and summarized. Based on the original excitation inrush logic,the paper proposes an integrated braking logic comprising "two-out-of-three" braking, phase current harmonic criteria and the maximum phase harmonic criteria, which solves the identification failure of excitation inrush with low harmonic ratio. The superiority and advancement of the scheme are proved by simulation and engineering application.
关键词(KeyWords):
励磁涌流;相电流判据;最大相谐波判据;改进与优化
inrush current;phase current criterion;maximum phase harmonic criterion;improvement and optimization
基金项目(Foundation): 内蒙古电力(集团)有限责任公司包头供电局科技项目(BG-ZXZB-2018-XSGL2C0101-2100)
作者(Author):
周浩,石磊,吕强
ZHOU Hao,SHI Lei,LYU Qiang
DOI: 10.19585/j.zjdl.202011011
参考文献(References):
- [1]HAMILTON R.Analysis of transformer inrush current and comparison of harmonic restraint methods in transformer protection[J].IEEE Transactions on Industry Applications,2013,49(4):1890-1899.
- [2]REKINA F,OUAHDI D.Analysis of the effects of magnetizing inrush current on power transformer differential protection[C]//Conference on Applications of Electrical Engineering.[S.l.:s.n.],2007.
- [3]LIN C E,CHENG C L,HUANG C L,et al.Investigation of magnetizing inrush current in transformers.II.Harmonic analysis[J].IEEE Transactions on Power Delivery,1993,8(1):255-263.
- [4]GIRGIS R S,TENYENHUIS E G.Characteristics of inrush current of present designs of power transformers[C]//2007 IEEE Power Engineering Society General Meeting.Tampa:IEEE,2007:1-6.
- [5]葛宝明,王祥珩,苏鹏声,等.电力变压器的励磁涌流判据及其发展方向[J].电力系统自动化,2003,27(22):1-5.
- [6]高中德,舒治淮,王德林.国家电网公司继电保护培训教材[M].北京:中国电力出版社,2009.
- [7]姚东晓,张凯,贺要锋,等.变压器多特征励磁涌流识别方案研究[J].电力系统保护与控制,2017,45(13):149-154.
- [8]金恩淑,李晓娜,宋晓刚,等.自适应变压器励磁涌流判据研究[J].电力系统保护与控制,2013,41(20):41-46.
- [9]孙庆森,张海峰,王猛,等.小波算法在变压器励磁涌流中的应用研究[J].电力系统保护与控制,2017,45(8):121-125.
- [10]FAIZ J,LOTFI-FARD S.A novel wavelet-based algorithm for discrimination of internal faults from magnetizing inrush currents in power transformers[J].IEEE Transactions on Power Delivery,2006,21(4):1989-1996.
- [11]卢雪峰.变压器励磁涌流多判据的模糊识别[D].保定:华北电力大学(河北),2007.
- [12]王昕,朱成柱,宋永明,等.模糊理论在识别变压器励磁涌流中的探讨[J].继电器,2000,28(8):46-47.
- [13]李海锋,王钢,李晓华,等.电力变压器励磁涌流判别的自适应小波神经网络方法[J].中国电机工程学报,2005,25(7):144-150.
- [14]刘喜梅,魏婉韵,于飞.基于人工神经网络的变压器励磁涌流的鉴别[J].低压电器,2007(19):57-60.
- [15]齐国政.变压器励磁涌流抑制技术研究[D].济南:山东大学,2017.
- [16]刘曦.浅析变压器励磁涌流引起的差动保护误动[J].浙江电力,2009,28(3):41-44.
- [17]吕珍,岳蔚,刘沛.变压器差动保护二次谐波制动判据的仿真研究[J].继电器,2003,31(6):69-72.
- [18]邱文征,陈德树.两种励磁涌流二次谐波制动判据的比较[J].电力自动化设备,1998,18(3):3-5.