200kV高压直流断路器操作拒动故障原因分析及建议Causes Analysis and Suggestions on Operation Rejection Failure of 200kV HVDC Circuit Breaker
张吼,杨勇,许琤,詹志雄,袁杰
ZHANG Hou,YANG Yong,XU Cheng,ZHAN Zhixiong,YUAN Jie
摘要(Abstract):
高压直流断路器是多端柔性直流输电工程换流站内重要的电气设备,直接关系到柔直系统运行的可靠性。根据±200 k V高压直流断路器在系统操作合闸过程中,出现的位置信号未及时返回控制系统,断路器后序无法进行分闸操作的故障现象,经报文分析判断和现场故障检测,得出故障原因是断路器开关内极柱分位传感器位置偏移,造成分位信号响应延迟、断路器拒动。最后通过将分位传感器调整至正常工作位置的方法解决了该问题,并提出了需要制定高压直流断路器检修规程及监控后台增加断路器操作次数统计功能的建议。
HVDC circuit breaker is important electrical equipment in the converter station of multi-terminal flexible direct current transmission project, which is directly related to the system operation reliability. According to the fault that the position signal of ±200 k V HVDC circuit breaker does not return to the control system in time during the operation and closing process of the system, the circuit breaker cannot be opened afterwards. Through messaging analysis and field fault detection, it is found that the fault reason is the displacement of the pole quantile sensor in the breaker switch, which results in the quantile signal response delay and operation rejection of circuit breaker. Finally, the problem is solved by adjusting the quantile sensor to the normal working position, and some suggestions are put forward that the maintenance rules of HVDC circuit breakers should be established and the statistical function of the operation times of the circuit breakers should be increased by monitoring and controlling backstage.
关键词(KeyWords):
多端柔性直流;高压直流断路器;拒动;分位传感器
multi-terminal flexible direct current;HVDC breaker;operation rejection;quantile sensor
基金项目(Foundation):
作者(Author):
张吼,杨勇,许琤,詹志雄,袁杰
ZHANG Hou,YANG Yong,XU Cheng,ZHAN Zhixiong,YUAN Jie
DOI: 10.19585/j.zjdl.201802010
参考文献(References):
- [1]郑占锋,邹积岩,董恩源,等.直流开断与直流断路器[J].高压电器,2006(6):445-449.
- [2]李宾宾,苟锐锋,张万荣.±800 k V特高压直流输电系统用直流断路器研究[J].能源评论,2007(3):8-11.
- [3]李晨,谷小博,杨智,等.舟山多端柔性直流输电示范工程零起升压方案研究[J].浙江电力,2015,34(7):16-19.
- [4]吴俊,方芳,赵晓明.柔性直流输电舟洋换流站无源HVDC启动试验中典型故障分析[J].浙江电力,2016,35(1):6-9.
- [5]许烽,江道灼,虞海泓,等.一种H桥型高压直流断路器的拓扑结构和故障隔离策略研究[J].浙江电力,2016,35(12):5-10.
- [6]魏晓光,高冲,罗湘,等.柔性直流输电网用新型高压直流断路器设计方案[J].电力系统自动化,2013,37(15):95-102.
- [7]FARHADI M,MOHAMMED O.Performance enhancement of actively controlled hybrid DC microgrid with pulsed load[J].IEEE Transactions on Industry Applications,2015,51(5):3570-3578.
- [8]高阳,贺之渊,王成昊,等.一种新型混合式直流断路器[J].电网技术,2016,40(5):1320-1325.
- [9]SANO K,TAKASAKI M.A surgeless solid-state DC circuit breaker for voltage-source-converter-based HVDCsystems[J].IEEE Transactions on Industry Applications,2014,50(4):2690-2699.
- [10]刘远,曹均正,魏晓光,等.串入耦合变压器高压直流断路器拓扑分析[J].智能电网,2015,3(12):1125-1130.