带电检测发现金属氧化物避雷器阻性电流异常的案例分析Case Analysis on Live Detection of Abnormal Resistive Current of MOA
刘安文,许甜田,张少成
LIU Anwen,XU Tiantian,ZHANG Shaocheng
摘要(Abstract):
从金属氧化物避雷器带电检测的方法和原理出发,分析了阻性电流带电检测对避雷器进行故障诊断的有效性。结合利用带电检测手段发现的设备故障案例,通过停电试验和解体分析证实了避雷器故障的原因是密封不良造成氧化锌阀片进水受潮。验证了带电检测在避雷器绝缘诊断中的有效性,同时提出了避雷器状态检测应注意的问题。
This paper analyzes effectiveness of the resistive current live test for MOA(Metal Oxide Arrester)on the basis of live test methods and principles of MOA. In combination with equipment failure found by live detection, It is confirmed that the cause of arrester failure is caused by moisture from poor sealing of MOA valve by outage test and disintegration analysis; validity of the detection of charged MOA insulation diagnosis is verified. Meanwhile, the paper proposes precautions in status detection of MOA in the future.
关键词(KeyWords):
带电检测;金属氧化物避雷器;状态检修;阻性电流
live detection;MOA;condition-based maintenance;resistive current
基金项目(Foundation):
作者(Author):
刘安文,许甜田,张少成
LIU Anwen,XU Tiantian,ZHANG Shaocheng
DOI: 10.19585/j.zjdl.2015.06.004
参考文献(References):
- [1]罗容波,王岩,李国伟,等.带电检测技术在避雷器状态诊断中的成功应用[J].电瓷避雷器,2011(6):53-57.
- [2]唐铁英.带电检测在氧化锌避雷器故障诊断中的应用[J].浙江电力,2012,31(4):40-42.
- [3]朱海貌,黄锐,夏晓波,等.金属氧化物避雷器带电检测数据异常的诊断及分析[J].电瓷避雷器,2012(2):68-76.
- [4]闫尚斌,唐领英,程艳霞.氧化锌避雷器带电检测在状态检修工作中的应用[J].电力学报,2013(6):201-202.
- [5]刘云鹏,夏巧群,李凌志.基于泄漏电流检测和红外成像技术的MOA故障综合诊断[J].高压电器,2007,43(2):133-135.
- [6]苏文宇,汪晓明,胡宏宇.220 k V金属氧化物避雷器带电测试异常的处理[J].电瓷避雷器,2008(3):32-37.
- [7]万四维.金属氧化物避雷器缺陷与阻性电流关系的分析探讨[J].电瓷避雷器,2007(5):31-33.