浙江电力

2010, v.29;No.174(10) 32-35

[打印本页] [关闭]
本期目录(Current Issue) | 过刊浏览(Archive) | 高级检索(Advanced Search)

600 MW超临界直流锅炉不投运锅炉循环泵启动控制
Startup Control of 600 MW Supercritical DC Boiler Without Enabling Circulating Pump

李彦猛,许五洲
LI Yan-meng,XU Wu-zhou(Zhejiang Zheneng Lanxi Power Generation Co.

摘要(Abstract):

介绍兰溪发电厂超临界直流锅炉启动系统的构成,对配置强制循环启动系统在因故障而不能投运锅炉循环泵时的启动方法进行深入分析,提出了通过疏水扩容器实现工质回收、减小给水量、分间隔投运油枪等措施。实践验证这些措施是可行的,可为同类型锅炉在不投运锅炉循环泵时的启动运行及调试提供参考。
This paper introduces the composition of supercritical DC boiler startup system in Lanxi Power Plant,analyzes in depth the start method of boiler with forced circulation startup system which is incapable of enabling circulating pump because of fault,proposes the measures such as working medium recycle with drain flash tank,feed water reduction,oil gun operation by intervals etc.,verifies the feasibility of these measures in practice and offers a reference for the startup,operation and commissioning of the same type of boilers without enabling circulating pump.

关键词(KeyWords): 直流锅炉;锅炉循环泵;启动控制
DC boiler;boiler circulating pump;startup control

Abstract:

Keywords:

基金项目(Foundation):

作者(Author): 李彦猛,许五洲
LI Yan-meng,XU Wu-zhou(Zhejiang Zheneng Lanxi Power Generation Co.

DOI: 10.19585/j.zjdl.2010.10.009