配电网消弧线圈优化控制策略Optimal Control Strategy for Arc Suppression Coil in Distribution Networks
吴文晓,许燕,杨学君,由静
WU Wenxiao,XU Yan,YANG Xuejun,YOU Jing
摘要(Abstract):
针对谐振电网消弧与选线难以兼顾的问题,提出了基于改进综合增量选线方法的消弧线圈优化控制策略。定义了一种新的零序电流综合增量,在脱谐度变化有限的情况下,增大故障线路与非故障线路间的差异性,从而提高选线的可靠性;根据交流熄弧条件,给出了基于改进零序电流综合增量选线方法、满足电弧不重燃条件下的消弧线圈控制策略。PSCAD仿真表明,改进后的零序电流综合增量法表征的故障特征更加显著,选线的正确性不受故障距离和过渡电阻影响,给出的优化控制策略能准确控制故障点的残流水平,兼顾消弧与选线2方面,具有极大的实用性。
To solve the difficult of dealing with both arc suppression and line selection, an improved method based on synthesis increment principle and optimal control strategy for arc suppression coil is proposed. A new synthesis increment of zero sequence current is defined. The method can expand the difference of the health and fault line with limited change of off tuning degree to improve line selection reliability. According to the AC arc suppression condition, a control strategy for arc suppression coil based on synthesis increment of zero sequence current and under non-combustion condition. PSCAD simulation shows that the improved zero sequence current synthesis incremental method shows more remarkable fault characteristics, and the correctness of line selection is not affected by fault distance and transition resistance. Considering arc suppression and line selection, the given strategy can accurately control residual current flow at the fault point and is of great practicability.
关键词(KeyWords):
谐振电网;单相接地故障;故障选线;零序电流;综合增量;消弧线圈;脱谐度;控制策略
resonant power system;single-phase grounding fault;fault line selection;zero sequence current;synthesis increment;arc suppression coil;off tuning degree;control strategy
基金项目(Foundation):
作者(Author):
吴文晓,许燕,杨学君,由静
WU Wenxiao,XU Yan,YANG Xuejun,YOU Jing
DOI: 10.19585/j.zjdl.201803010
参考文献(References):
- [1]王清亮.单相接地故障分析与选线技术[M].北京:中国电力出版社,2013.
- [2]董新洲,毕见广.配电线路暂态行波的分析和接地选线研究[J].中国电机工程学报,2005,25(4):1-6.
- [3]贾清泉,刘连光,杨以涵,等.应用小波检测故障突变特性实现配电网小电流故障选线保护[J].中国电机工程学报,2001,21(10):79-83.
- [4]曾祥君,尹项根,于永源,等.基于注入变频信号法的经消弧线圈接地系统控制与保护新方法[J].中国电机工程学报,2000,20(1):30-33.
- [5]李天云,祝磊,王飞,等.基于数学形态谱的配电网接地选线新方法[J].电力自动化设备,2009,29(2):35-38.
- [6]唐轶,陈奎,陈庆,等.导纳互差之绝对值和的极大值法小电流接地选线研究[J].中国电机工程学报,2005,25(6):49-54.
- [7]齐郑,刘宝柱,王璐,等.广域残流增量选线方法在辐射状谐振接地系统中的应用[J].电力系统自动化,2006,30(3):84-88.
- [8]林湘宁,黄小波,翁汉琍,等.基于分布参数模型的比相式单相故障单端测距算法[J].电网技术,2007,31(9):74-79.
- [9]王宾,董新洲,薄志谦,等.特高压长线路单端阻抗法单相接地故障测距[J].电力系统自动化,2008,32(14):25-29.
- [10]蔡旭.基于偏磁消弧线圈的综合增量法单相接地保护[J].电力系统自动化,2003,27(20):68-72.
- [11]陈奎,韦晓广,陈景波,等.基于样本数据处理和AD-ABOOST的小电流接地故障选线[J].中国电机工程学报,2014,34(34):28-37.
- [12]宋大伟.基于智能跟踪原理的消弧线圈控制装置[D].济南:山东大学,2007.
- [13]连鸿波,谭伟璞,裴善鹏,等.谐振接地电网预随调补偿方式及其实现[J].电力系统自动化,2005,29(21):83-88.
- [14]李晓波.柔性零残流消弧线圈的研究[D].徐州:中国矿业大学,2010.