浙江电力

2012, v.31;No.199(11) 34-37

[打印本页] [关闭]
本期目录(Current Issue) | 过刊浏览(Archive) | 高级检索(Advanced Search)

烟气排放连续监测系统数据异常的分析及处理
Analysis and Treatment on Abnormal Data of Continuous Emission Monitoring System

卢毓东,谢宏海,陆建伟
LU Yu-dong1,XIE Hong-hai2,LU Jian-wei1(1.Z(P)EPC Electric Power Research Institute

摘要(Abstract):

以北仑发电厂6号机组的烟气连续监测系统数据异常为例,分析了SO2数据异常的特征,提出了故障分析与诊断方法,得出了SO2数据异常的最终原因是红外气体分析仪内部软件CO过补偿所致的结论,成功解决了困扰一年多的测量难题。
Taking abnormal data of continuous emission monitoring system(CEMS) of unit 6 in Beilun Power Plant as an example,the paper analyzes the characteristics of the abnormal data of SO2 and proposes the fault analysis and diagnosis method.It concludes that the abnormal data of SO2 is fundamentally caused by overcompensation of CO in infrared gas analyzer,successfully solving the difficult problem in measurement that lasts one year or more.

关键词(KeyWords): CEMS;SO2;突变至零;交叉干扰
CEMS;SO2;return to zero;cross interference

Abstract:

Keywords:

基金项目(Foundation):

作者(Author): 卢毓东,谢宏海,陆建伟
LU Yu-dong1,XIE Hong-hai2,LU Jian-wei1(1.Z(P)EPC Electric Power Research Institute

DOI: 10.19585/j.zjdl.2012.11.012