浙江电力

2012, v.31;No.199(11) 14-16

[打印本页] [关闭]
本期目录(Current Issue) | 过刊浏览(Archive) | 高级检索(Advanced Search)

高土壤电阻率变电站的降阻探讨
Investigation on Resistance-reduction in Substation with High Earth Resistivity

柯荷秀
KE He-xiu(Hangzhou Electric Power Design Institute

摘要(Abstract):

针对高土壤电阻率的接地网,根据变电站现场实际情况,采取外延接地体、扩大外延接地网、换入低电阻率土壤等综合降阻措施来降低接地电阻,这样既有效又经济,校核了接地电阻偏高接地网的接触电压和跨步电压。
In accordance with grounding grid with high earth resistivity and practical situation of substation,comprehensive measures such as extension of ground body,expansion of extended grounding grid and replacement by low-resistivity earth are taken to lower ground resistance,which is effective and efficient and verifies high grounding resistance,touch voltage and step voltage.

关键词(KeyWords): 变电站;高土壤电阻率;接地电阻;降阻
substation;high earth resistivity;ground resistance;resistance reduction

Abstract:

Keywords:

基金项目(Foundation):

作者(Author): 柯荷秀
KE He-xiu(Hangzhou Electric Power Design Institute

DOI: 10.19585/j.zjdl.2012.11.005