终端变电站单相接地故障时变压器中性点过电压仿真与分析
Simulation and Analysis of Transformer Neutral Point Overvoltage During Single-phase Grounding Fault of Terminal Substation

周象贤,孙翔,金佳敏
ZHOU Xiangxian,SUN Xiang,JIN Jiamin

摘要(Abstract):

110 k V与220 k V变电站中存在部分中性点不接地变压器,其中性点与地间一般接有保护间隙。运行经验表明,终端变中不接地变压器在进线单相接地故障时容易发生间隙击穿并导致间隙过流保护动作,但目前的研究都没有解释为何非终端变不容易发生此类事故。通过典型的终端变与非终端变变压器中性点过电压的仿真,对比分析了这两类变电站在进线单相接地故障时的电气量变化过程,从而解释了终端变易发生保护动作的原因。
Some transformer neutral points in 110 k V and 220 k V substations are not grounded, and there is usually a protection gap between neutral point and ground. The operation experience shows that the neutral gap of transformer in terminal substation is prone to be broken down during single phase grounding fault,leading to over current protection of protection gap. However, the existing research has not explained why the non-terminal substations are invulnerable to such accidents. Through simulation on neutral point overvoltage of transformers in both terminal and non-terminal substations, the paper compares and analyzes electrical quantity alternation of the two substations during single-phase grounding fault, which explains the reason of protection action that frequently occurs in terminal substation.

关键词(KeyWords): 终端变电站;中性点;过电压;仿真
terminal substation;neutral point;overvoltage;simulation