古越—舜江双线停役后运行方式优化的研究Research on Operation Mode Optimization After Outage of Guyue and Shunjiang Lines
李磊,孙维真,倪秋龙,丁历威
LI Lei1,SUN Wei-zhen1,NI Qiu-long1,DING Li-wei2(1.Zhejiang Electric Power Dispatching and Communication Center
摘要(Abstract):
由于高铁上虞牵引站线路的跨越施工,500 kV古越—舜江双线同时停役,导致该片电网稳定性严重下降。为降低电网运行风险,从潮流计算、暂态稳定分析、短路电流校核和小干扰分析等多个方面对运行方式的调整进行深入研究。研究结果表明:采用齐贤—兰亭双线合环(陪停兰亭3号主变)或太安—中纺双线合环的方式可达到优化运行方式的目的。
The outage of the two 500 kV lines of Guyue and Shunjiang caused by the line crossing construction of the Shangyu high-speed rail station decreases the grid stability in that area.This paper conducts the in-depth research on the operation mode adjustment in terms of the power flow calculation,transient stability analysis,short-circuit current verification and small signal stability analysis in order to reduce the grid operation risk.The result shows that enabling closed-loop operation of Qixian and Lanting lines(disabling the third transformer of Lanting station meanwhile) or Tai′an and Zhongfang lines can achieve the goal of operation mode optimization.
关键词(KeyWords):
500kV双线;运行方式;调整;潮流;暂态稳定;短路电流
two 500 kV lines;operation mode;adjustment;power flow;transient stability;short-circuit current
基金项目(Foundation):
作者(Author):
李磊,孙维真,倪秋龙,丁历威
LI Lei1,SUN Wei-zhen1,NI Qiu-long1,DING Li-wei2(1.Zhejiang Electric Power Dispatching and Communication Center
DOI: 10.19585/j.zjdl.2012.05.001
参考文献(References):
- 李继红,陆春良,韩连.华东与福建联网后对浙江电网影响的分析[J].浙江电力,2002,21(2):6-9.
- 毛雪雁,孙黎滢,徐政.浙江特高压直流混合电网系统稳定性研究[J].浙江电力,2010,29(6):1-4.
- 张勇,王云辉,沈建涛,等.输电网短路电流计算[J].电网技术,2007,31(1):39-42.
- 吴政球,匡文凯,杨洪波,等.单机等面积法电力系统暂态稳定分析[J].电力系统及其自动化学报,2010,22(4):64-70.
- 吴政球,周野,匡文凯,等.基于参考机的单机等面积暂态稳定分析[J].湖南大学学报(自然科学版),2011,38(6):49-54.
- 武冠英,姚智慧,彭金平,等.电力系统暂态稳定协调控制策略研究综述[J].电力与电工,2010,30(4):9-11.
- 司马瑞,王克文.多运行方式下的概率暂态稳定计算[J].电力系统保护与控制,2010,38(7):7-11.
- 周泽昕,马世英,汤涌,等.电力系统稳定计算中500 kV线路故障清除时间的研究[J].中国电力,2002,35(2):44-48.
- 刘涛,宋新立,汤涌,等.特征值灵敏度方法及其在电力系统小干扰稳定分析中的应用[J].电网技术,2010,34(4):82-87.
- ROUCO L,PAGOLA F L.An eigenvalue sensitivity approach to location and controller design of controllable series capacitors for dampingpower system oscillations[J].IEEE Transactions on Power Systems,1997,12(4):16601666.
- 500kV双线
- 运行方式
- 调整
- 潮流
- 暂态稳定
- 短路电流
two 500 kV lines - operation mode
- adjustment
- power flow
- transient stability
- short-circuit current
- 李磊
- 孙维真
- 倪秋龙
- 丁历威
LI Lei1 - SUN Wei-zhen1
- NI Qiu-long1
- DING Li-wei2(1.Zhejiang Electric Power Dispatching and Communication Center
- 李磊
- 孙维真
- 倪秋龙
- 丁历威
LI Lei1 - SUN Wei-zhen1
- NI Qiu-long1
- DING Li-wei2(1.Zhejiang Electric Power Dispatching and Communication Center