调相机接入对浙江电网的影响研究Research on the Impact of Synchronous Condenser on Zhejiang Power Grid
赵一琰,华文,邓晖,黄弘扬,宋春燕
ZHAO Yiyan,HUA Wen,DENG Hui,HUANG Hongyang,SONG Chunyan
摘要(Abstract):
随着交直流混联电网的不断发展,交直流系统交互响应特性日趋复杂,引入调相机等动态无功补偿装置以提升电网稳定性已成为当前研究热点。基于浙江交直流电网基本运行特征,分析了两大特高压直流落点金华、绍兴换流站加装调相机对电网安全稳定水平的影响。分别针对交流系统故障及直流系统故障2种工况,通过对比调相机接入前后电压响应特性,分析了调相机在特高压交直流系统故障中的作用。仿真结果表明:调相机的接入有利于提高直流系统换相失败抵御能力,缩小事故中交流电网电压波动范围,提升事故后地区电压稳定水平。
With the development of hybrid AC/DC systems, the interactive influence between AC and DC systems becomes more complicated than before. Power grid stability improvement by the introduction of dynamic reactive power compensation installations like synchronous condensers has now become a hot research topic. Based on the operation characteristics of Zhejiang AC/DC power grid, the influence of synchronous condensers in Jinhua and Shaoxing converter stations on the security and stability level of power grid is analyzed.By comparing the voltage response characteristics with and without synchronous condensers in AC/DC system faults, the impacts of synchronous condensers on UHVAC/DC system faults are investigated respectively. The simulation result shows that the application of synchronous condensers is able to reduce commutation failure probability of DC system, narrow down voltage fluctuation range during accidents and improve system voltage stability after accidents.
关键词(KeyWords):
交直流电网;调相机;电压稳定;换相失败
AC/DC systems;synchronous condenser;voltage stability;commutation failure
基金项目(Foundation):
作者(Author):
赵一琰,华文,邓晖,黄弘扬,宋春燕
ZHAO Yiyan,HUA Wen,DENG Hui,HUANG Hongyang,SONG Chunyan
DOI: 10.19585/j.zjdl.201801002
参考文献(References):
- [1]覃琴,郭强,周勤勇,等.国网“十三五”规划电网面临的安全稳定问题及对策[J].中国电力,2015,48(1):25-32.
- [2]邵瑶,汤涌.多馈入交直流混合电力系统研究的综述[J].电网技术,2009,33(17):24-30.
- [3]欧开健,荆勇,任震.多馈入直流输电系统换流母线电压稳定性评估模型和算法[J].电力自动化设备,2003,(9):23-26.
- [4]DENIS L,ANDERSSON G.Power stability analysis of multi-infeed HVDC systems[J].Power Delivery,IEEE Transactions on,1998,13(3):923-931.
- [5]HE JINGBO,LI MINGJIE,YI JUN,et al.Research on dynamic characteristics and countermeasures of AC-DC hybrid power system with large scale HVDC transmission[C]//2014 International Conference on Power System Technology,Chengdu,China,December 18,2014.
- [6]林伟芳,汤涌,卜广全.多馈入交直流系统电压稳定性研究[J].电网技术,2008,32(11):7-12.
- [7]张勇军,韩东昆,刘巍.受端电网静态/动态无功补偿综合优化[J].电力自动化设备,2009,29(3):32-35.
- [8]欧开健,任震,荆勇.直流输电系统换相失败的研究(一):换相失败的影响因素分析[J].电力自动化设备,2003,23(5):5-9.
- [9]朱韬析,王超.天广直流输电系统换相失败的分析及处理[J].高电压技术,2008,34(8):1769-1773.
- [10]王晶,梁志峰,江木,等.多馈入直流同时换相失败案例分析及仿真计算[J].电力系统自动化,2015,39(4):141-146.
- [11]李国栋,皮俊波,郑力,等.±500 k V林枫直流双极闭锁故障案例仿真分析[J].电网技术,2014,38(4):877-881.
- [12]杨雄平,罗向东,李扬絮,等.南方电网直流闭锁故障时受端系统电压稳定问题分析[J].电力系统保护与控制,2008,36(22):40-43.
- [13]凌卫家,孙维真,叶琳,等.浙江交直流混联电网特性分析及运行控制[J].浙江电力,2016,35(9):8-14.
- [14]苏永春,程时杰,文劲宇,等.电力系统电压稳定性及其研究现状(二)[J].电力自动化设备,2006,26(7):97-100.
- [15]潘仁秋,何其伟,陈俊.大型调相机的保护配置及其实现[J].江苏电机工程,2011,30(6):45-47.
- [16]任丕德,刘发友,周胜军.动态无功补偿技术的应用现状[J].电网技术,2004,28(23):81-83.
- [17]高强,张小聪,施正钗,等.±800 k V宾金直流双极闭锁故障对浙江电网的影响[J].电网与清洁能源,2014,30(11):47-51.
- [18]毛雪雁,孙黎滢,徐政,等.浙江特高压交直流混合电网系统稳定性研究[J].浙江电力,2010,29(6):1-4.
- [19]徐蔚,黄弘扬,徐政.PSS/E的直流模型及BPA直流系统响应特性的比较[J].高压电器,2013,49(12):116-122.
- [20]徐政,唐庚,黄弘扬,等.消解多直流馈入问题的两种新技术[J].南方电网技术,2013,7(1):6-14.
- [21]张宁宇,刘建坤,周前,等.同步调相机对直流逆变站运行特性的影响分析[J].江苏电机工程,2016,35(3):17-20.