1000kV线路高压电抗器油中CO和CO2产气规律研究Generation Regularity of CO and CO2 in High Voltage Reactor Oil of 1000 kV Lines
徐庆峰,黄秀娟,尹恒,刘杰
XU Qingfeng,HUANG Xiujuan,YIN Heng,LIU Jie
摘要(Abstract):
针对浙江省3座特高压变电站1 000 kV线路高抗CO和CO_2浓度持续攀升现象,调取了2015年1月至2016年8月线路高抗油色谱在线监测数据,分析了CO和CO_2的浓度和产气速率,以及特征比值的变化趋势,获得了CO和CO_2的产气规律,为1 000 kV线路高抗的在线监测和故障诊断研究奠定基础。结果表明:1 000 kV线路高抗CO和CO_2气体浓度持续攀升属于正常现象,其产气规律基本相同,即随着运行时间的增加,CO和CO_2浓度呈不断上升趋势;CO和CO_2产气速率呈先上升后下降再上升趋势;特征比值呈先降低后增长再降低的趋势。
Based on the fact that the concentrations of CO and CO_2 in high voltage reactors of 1 000 kV lines of three ultra-high voltage substations in Zhejiang province became increasingly high,online monitored oil chromatogram data of high voltage reactors from January 2015 to August 2016 is obtained to analyze concentrations and generation rates of CO and CO_2 as well as the development trend of their characteristic ratio to conclude the generation regularity for the purpose of laying a foundation for online monitoring and fault diagnosis for high voltage reactors of 1 000 kV lines.The result shows that it is normal that the concentrations of CO and CO_2 keep rising,and the generation regularity of them is identical,meaning with the increase of operation time,the concentrations of CO and CO_2 continued to increase;the generation rates of CO and CO_2 increase first,then decline,and finally increase again;the characteristic ratio shows a trend of decline first,then increases,finally declines again.
关键词(KeyWords):
特高压变电站;高压并联电抗器;CO;CO2;浓度;产气速率;特征比值
ultra-high voltage substation;high-voltage parallel reactor;CO;CO2;concentration;gas generation rate;characteristic ratio
基金项目(Foundation):
作者(Author):
徐庆峰,黄秀娟,尹恒,刘杰
XU Qingfeng,HUANG Xiujuan,YIN Heng,LIU Jie
DOI: 10.19585/j.zjdl.2017.03.006
参考文献(References):
- [1]张志强,韩先才,班连庚,等.1 000 k V交流特高压试验示范工程变电站110 k V侧电容器组串抗率分析[J].中国电力,2007,40(12):36-42.
- [2]张丽,徐玉琴.并联电抗器在超特高压电网中应用及发展[J].电力自动化设备,2007,27(4):75-78.
- [3]夏强峰,袁均祥,屠晔炜,等.输电线路交流感应电压消除装置的研制[J].浙江电力,2015,34(7):66-68.
- [4]王伟,夏中原,韩金华,等.特高压电抗器的现场交流耐压试验[J].高压电器,2010,46(1):61-63.
- [5]何毅帆.基于流体分析的并联电抗器局部放电的识别与定位研究[J].浙江电力,2015,34(9):10-14.
- [6]DL/T 722-2000变压器油中溶解气体分析和判断导则[S].北京:中国电力出版社,2000.
- [7]刘勇辉.利用特征气体排列图判断电力变压器潜伏性故障类型[J].变压器,2005,42(5):48-50.
- [8]张勇.基于油中溶解气体分析的变压器在线监测与故障诊断[D].北京:华北电力大学,2013.
- [9]张挺,王章启,魏天魁.变压器油中溶解气体在线监测系统的研究[J].高压电器,2005,41(1):21-23.
- [10]杨振勇.《变压器油中溶解气体分析和判断导则》判断变压器故障的探讨[J].变压器,2008,45(10):24-27.
- [11]董艳.变压器固体绝缘的劣化与CO和CO2含量的关系[J].变压器,2012,49(2):47-48.
- [12]范玉华,刘富家,于秀华.大型变压器油中CO和CO2含量判断指标的确定[J].东北电力技术,1994(1):6-10.
- [13]陈伟根.以油中多种气体为特征量的变压器绝缘在线监测及故障诊断技术研究[D].重庆:重庆大学,2003.
- [14]JOHN M HUNT,何生.根据阿伦尼乌斯方程用时间-温度指数图模拟石油生成[J].地质科学译丛,1992,9(3):37-45.
- [15]刘先勇.从变压器油中分离故障特征气体的研究[J].电力系统自动化,2005,29(2):56-60.
- [16]罗建波.基于DGA的电力变压器故障诊断技术研究[D].杭州:浙江大学,2005.
- [17]李家明,袁静.对变压器油中溶解CO和CO2气体的分析[J].吉林水利,2009(1):58-59.
- 特高压变电站
- 高压并联电抗器
- CO
- CO2
- 浓度
- 产气速率
- 特征比值
ultra-high voltage substation - high-voltage parallel reactor
- CO
- CO2
- concentration
- gas generation rate
- characteristic ratio