Analysis on Misoperation of Differential Protection for Main Transformer Caused by Excitation Inrush Current

孔飘红,余彬,韩荣杰
KONG Piao-hong,YU Bin,HAN Rong-jie(Xiaoshan Power Supply Bureau

摘要(Abstract):

主变空载投运时,由于励磁涌流引起差动保护误动作时有发生。结合一起110 kV主变发生因励磁涌流引起的差动保护误动故障,对励磁涌流的特性、保护误动作的原因、整定计算等方面进行了分析,并就如何躲开励磁涌流的影响进行了探讨。
When no-load main transformers are put in operation,misoperation of differential protection often occurs because of excitation inrush current.This paper analyzes the characteristics of excitation inrush current,misoperation causes of differential protection,setting calculation etc.based on the misoperation of differential protection for the 110 kV main transformer caused by excitation inrush current,and discusses the countermeasures to eliminate the influence of excitation inrush current.

关键词(KeyWords): 主变;差动保护;励磁涌流;二次谐波制动;防误动
main transformer;differential protection;excitation inrush current;secondary harmonic restraint;anti-misoperation