输电线路绝缘核相测试抗干扰方法的研究Research on Method of Anti-interference for Insulation Phase Checking Test of Transmission Lines
赵寿生,徐健,吴尊东,陈欣华
ZHAO Shou-sheng,XU Jian,WU Zun-dong,CHEN Xin-hua(Jinhua Electric Power Bureau
摘要(Abstract):
为了消除感应电压对输电线路绝缘核相测试的干扰,介绍了一种利用串联谐振抗干扰的方法,与传统试验方法测试结果相比,采用串联谐振抗干扰方法后,线路测试结果准确并有着良好的一致性,同时解决了在较高感应电压下不能测试输电线路绝缘电阻的问题。
In order to eliminate the interference of induced voltage in the test of insulation phase checking for transmission lines,an anti-interference method of serial resonance is described.Through the comparison with the results of traditional test methods,it shows that the proposed method results are accurate and consistent and solves the problem of being unable to measure the insulation resistance of transmission lines at high induced voltages.
关键词(KeyWords):
输电线路;串联谐振;感应电压;绝缘水平
transmission line;serial resonance;induced voltage;insulation level
基金项目(Foundation):
作者(Author):
赵寿生,徐健,吴尊东,陈欣华
ZHAO Shou-sheng,XU Jian,WU Zun-dong,CHEN Xin-hua(Jinhua Electric Power Bureau
DOI: 10.19585/j.zjdl.2012.05.003