基于IIDG故障电流迭代计算的配电网自适应零序电流保护An adaptive zero-sequence current protection scheme for distribution networks based on iterative fault current calculation of IIDGs
李娟,姜云龙,朱睿,杨雄
LI Juan,JIANG Yunlong,ZHU Rui,YANG Xiong
摘要(Abstract):
由于IIDG(逆变型分布式电源)的出力具有一定的波动性,配电网的故障特性也发生了变化,这给继电保护定值整定带来了困难。以典型的含IIDG小电阻接地系统为例,首先,分析了IIDG接入后在单相接地故障时的零序电流特性,阐明了IIDG对传统零序电流速断保护的影响。然后,在此基础上给出了IIDG故障电流求解算法,并提出了一种零序电流自适应保护方案,以提高保护的选择性和可靠性,适应高渗透率新能源的接入。最后,对所提方法进行仿真验证,证明了该方法的有效性和实用性。
Due to the inherent output fluctuations of inverter-interfaced distributed generators(IIDGs), the fault characteristics of distribution networks have changed, posing challenges for relay protection setting. Taking a typical low-resistance grounding system with IIDG as an example, this paper first analyzes the zero-sequence current characteristics during single phase-to-ground faults after IIDG integration and clarifies its impact on traditional instantaneous zero-sequence current protection. Based on this analysis, a fault current calculation algorithm for IIDGs is proposed, along with an adaptive zero-sequence current protection scheme to enhance protection selectivity and reliability, thereby accommodating high-penetration renewable energy integration. Finally, simulation results validate the effectiveness and practicality of the proposed method.
关键词(KeyWords):
IIDG;故障电流;自适应零序电流保护;单相接地故障
IIDG;fault current;adaptive zero-sequence current protection;single phase-to-ground fault
基金项目(Foundation): 国家电网有限公司科技项目(J2023102)
作者(Author):
李娟,姜云龙,朱睿,杨雄
LI Juan,JIANG Yunlong,ZHU Rui,YANG Xiong
DOI: 10.19585/j.zjdl.202507011
参考文献(References):
- [1]尹项根,王义凯,谭力铭,等.基于双频有源调控的大型机组定子接地故障电弧抑制及自适应保护[J].电力系统保护与控制,2023,51(6):1-9.YIN Xianggen,WANG Yikai,TAN Liming,et al.Dualfrequency active regulation-based arc suppression and adaptive protection for a stator ground fault in large generators[J]. Power System Protection and Control,2023,51(6):1-9.
- [2]ZHANG P,HOU M,LIANG R,et al.Incipient fault detection of medium-voltage distribution cable systems using time-frequency analysis of grounding wire currents[J].IEEE Transactions on Smart Grid,2025,16(1):74-86.
- [3]住房和城乡建设部,国家发展改革委:住房和城乡建设部,国家发展和改革委员会.城乡建设领域碳达峰实施方案[EB/OL].北京:住房城乡建设部网站,2022[2022-06-30]. https://www. gov. cn/zhengce/zhengceku/2022-07/13/content_5700752.htm.
- [4]ZHANG P,KONG L C,LIANG R,et al.Fault location method for three-core cable using amplitude ratio of shieldgrounding wire currents[J].IEEE Transactions on Industrial Informatics,2023,19(6):7456-7467.
- [5]廖芳群,李海锋,陈嘉权,等.小电阻接地系统高灵敏性接地故障区段定位方法[J].电力系统保护与控制,2021,49(21):150-158.LIAO Fangqun,LI Haifeng,CHEN Jiaquan,et al. High sensitive ground fault location in a low-resistance grounded system[J].Power System Protection and Control,2021,49(21):150-158.
- [6]高美金,诸言涵,张啸,等.含逆变型分布式电源配电网的中性点接地电阻选取[J].浙江电力,2022,41(3):11-19.GAO Meijin,ZHU Yanhan,ZHANG Xiao,et al.Selection of neutral grounding resistance of distribution networks containing inverter-type distributed power supply[J].Zhejiang Electric Power,2022,41(3):11-19.
- [7]国家市场监督管理总局,国家标准化管理委员会.光伏发电并网逆变器技术要求:GB/T 37408—2019[S].北京:中国标准出版社,2019.
- [8]姜淼,石勇,徐光福,等.大容量逆变型分布式电源接入对配电网单相接地检测的影响[J].浙江电力,2023,42(2):9-16.JIANG Miao,SHI Yong,XU Guangfu,et al.Analysis of the impact of large capacity IIDGs on single-phase grounding detection of distribution networks[J].Zhejiang Electric Power,2023,42(2):9-16.
- [9]任伟,薛永端,徐丙垠,等.小电阻接地系统高阻接地故障纵联差动保护[J].电网技术,2021,45(8):3276-3282.REN Wei,XUE Yongduan,XU Bingyin,et al.Longitudinal differential protection of high resistance grounding faults in low-resistance grounding system[J].Power System Technology,2021,45(8):3276-3282.
- [10]雷杨,杨帆,汪洋,等.基于双模功能的配电网单相接地故障灵活处理策略[J].供用电,2020,37(8):60-67.LEI Yang,YANG Fan,WANG Yang,et al.The flexible strategy of single phase grounding fault in distribution network based on dual mode function[J].Distribution&Utilization,2020,37(8):60-67.
- [11]李海锋,陈嘉权,曾德辉,等.小电阻接地系统高灵敏性零序电流保护[J].电力自动化设备,2018,38(9):198-204.LI Haifeng,CHEN Jiaquan,ZENG Dehui,et al.High sensitive zero-sequence current protection for low-resistance grounding system[J]. Electric Power Automation Equipment,2018,38(9):198-204.
- [12]许庆强,许扬,周栋骥,等.小电阻接地配电网线路保护单相高阻接地分析[J].电力系统自动化,2010,34(9):91-94.XU Qingqiang,XU Yang,ZHOU Dongji,et al. Analysis of distribution network line relay protection during singlephase high-resistance grounding faults in low resistance neutral grounded system[J]. Automation of Electric Power Systems,2010,34(9):91-94.
- [13]牛原,秦文萍,夏福良,等.基于零序电流投影分量比值的小电阻接地系统故障保护[J].太原理工大学学报,2021,52(6):928-935.NIU Yuan,QIN Wenping,XIA Fuliang,et al.Fault protection based on the ratio of zero-sequence current projection components for low-resistance grounding system[J].Journal of Taiyuan University of Technology,2021,52(6):928-935.
- [14]薛永端,汪洋,徐丙垠.小电阻接地系统高灵敏度阶段式零序过电流保护[J].中国电机工程学报,2020,40(19):6217-6227.XUE Yongduan,WANG Yang,XU Bingyin.High sensitive zero-sequence stage current protection for lowresistance grounding system[J].Proceedings of the CSEE,2020,40(19):6217-6227.
- [15]张晓鹏,白洁,孙乃君,等.基于特征融合的GA-SVM配电网单相接地故障选线方法[J].电测与仪表,2025,62(1):140-148.ZHANG Xiaopeng,BAI Jie,SUN Naijun,et al.GA-SVM method for single-phase grounding fault line selection in distribution network based on feature fusion[J].Electrical Measurement&Instrumentation,2025,62(1):140-148.
- [16]杨伟涛,曾德辉,汪隆君,等.逆变型分布式电源接入对小电阻接地系统馈线零序电流保护的影响[J].电力自动化设备,2018,38(9):162-168.YANG Weitao,ZENG Dehui,WANG Longjun,et al.Influence of inverter interfaced distributed generators on zero-sequence current protection for feeder of low resistance grounding system[J]. Electric Power Automation Equipment,2018,38(9):162-168.
- [17]韦明杰,王聪博,余越,等.适用高比例分布式光伏接入的配电网多级保护优化配置方案[J].电力系统自动化,2023,47(22):55-65.WEI Mingjie,WANG Congbo,YU Yue,et al. Optimal configuration scheme of multi-staged protection in distribution network for integration of high proportion of distributed photovoltaic[J]. Automation of Electric Power Systems,2023,47(22):55-65.
- [18]乔一达,吴红斌,吴通华,等.含逆变型分布式电源的配电网分区域电流保护[J].电工技术学报,2022,37(增刊1):134-144.QIAO Yida,WU Hongbin,WU Tonghua,et al.A partitioned current protection scheme of distribution network with inverter interfaced distributed generator[J].Transactions of China Electrotechnical Society,2022,37(S1):134-144.
- [19]刘红政,左毅,王伦,等.基于FTU的新型配电网单相接地故障研究[J].电力电容器与无功补偿,2024,45(6):76-82.LIU Hongzheng,ZUO Yi,WANG Lun,et al.Research on single phase ground fault of new distribution network based on FTU[J]. Power Capacitor&Reactive Power Compensation,2024,45(6):76-82.
- [20]王伟杰,曾鑫洁,徐远途,等.基于正序突变量相轨迹辨识的可再生能源配电网电流保护[J].发电技术,2024,45(4):753-764.WANG Weijie,ZENG Xinjie,XU Yuantu,et al.Renewable energy distribution network overcurrent protection based on positive-sequence sudden-change component locus identification[J]. Power Generation Technology,2024,45(4):753-764.
- [21]廖德辉,金鑫,田君杨,等.灵活接地配电网单相接地故障全过程特征分析[J].智慧电力,2024,52(5):90-97.LIAO Dehui,JIN Xin,TIAN Junyang,et al.Analysis of the entire process characteristics of single phase-to-ground faults in flexible grounded distribution networks[J].Smart Power,2024,52(5):90-97.
- [22]吴任博,黄奕俊.高比例可再生能源接入下含自愈性能的分布式配电网重构策略研究[J].发电技术,2024,45(5):975-982.WU Renbo,HUANG Yijun. Research on reconfiguration strategy of distributed distribution network with selfhealing performance under high-proportion renewable energy access[J]. Power Generation Technology,2024,45(5):975-982.
- [23]曾德辉,王钢,郭敬梅,等.含逆变型分布式电源配电网自适应电流速断保护方案[J].电力系统自动化,2017,41(12):86-92.ZENG Dehui,WANG Gang,GUO Jingmei,et al.Adaptive current protection scheme for distribution network with inverter-interfaced distributed generators[J].Automation of Electric Power Systems,2017,41(12):86-92.
- [24]和敬涵,宋元伟,李猛,等.基于信息指纹的柔性直流线路差动保护[J].中国电机工程学报,2022,42(13):4800-4811.HE Jinghan,SONG Yuanwei,LI Meng,et al.Differential protection of flexible DC line based on information fingerprint[J].Proceedings of the CSEE,2022,42(13):4800-4811.
- [25]高维良,高厚磊,徐彬,等.5G用作配电网差动保护通道的可行性分析[J].电力系统保护与控制,2021,49(8):1-7.GAO Weiliang,GAO Houlei,XU Bin,et al. Feasibility analysis of adopting 5G in differential protection of distribution networks[J]. Power System Protection and Control,2021,49(8):1-7.