一种针对桥断路器双TA布置方式的差动保护逻辑
A Differential Protection Criterion for Double TA Distribution of Bridge Circuit Breaker

陈锡磊,胡彬,张思,陆海清
CHEN Xilei,HU Bin,ZHANG Si,LU Haiqing

摘要(Abstract):

根据桥断路器双TA布置的内桥变电站的接线特点,分析了在桥断路器与两侧TA之间发生故障时的主变差动保护动作行为,指出在上述位置发生故障时将出现全站停电的情况。据此,提出了改进的差动保护逻辑,并详细分析了该差动保护逻辑在变电站不同运行方式下的动作行为,能够最大程度地避免全站停电,提高桥断路器双TA布置的内桥变电站的供电可靠性。
Aiming at the wiring characteristics of inner bridge substation with double TA distribution of bridge circuit breaker, the paper analyzes differential protection action of main transformer when faults occur between bridge circuit breaker and TA at its both sides. It is indicates that there will be outage when faults occurs in the aforementioned location. Therefore, the paper presents an improved differential protection logic and expounds its protection action under different operation modes, for the purpose of avoiding outage of the entire substation to the maximum extent and improving power supply reliability of inner bridge substation with bridge circuit breaker equipped with double TA.

关键词(KeyWords): 内桥接线;双TA布置;全站停电;差动保护
inner bridging wiring;double TA distribution;substation outage;differential protection