GIS带电检测中超声波干扰信号的多维度综合分析方法研究Research on The Multi-dimensional Comprehensive Analysis Method of Ultrasonic Interference Signal in Live Detection of GIS
杜伟,杨勇,梅冰笑,董雪松,邵先军
DU Wei,YANG Yong,MEI Bingxiao,DONG Xuesong,SHAO Xianjun
摘要(Abstract):
超声波局部放电检测法被广泛应用于现场GIS带电检测工作中,但该方法在现场实测时,受多种因素影响产生的干扰信号严重影响了缺陷诊断的准确性。通过对现场检测的超声波异常信号开展分析,综合屏蔽法、相位法、时差定位法等手段对现场测试数据进行诊断。该方法可用于指导现场超声波检测时干扰信号的分析与排除。
Ultrasonic-based partial discharge detection method is widely used in live detection of field GIS.But in actual field detection, the accuracy of defect diagnosis of this method is seriously affected by the interference signal due to various factors. In this paper, the abnormal ultrasonic signal in field detection is analyzed, and through the shielding method, phase method, time difference location method the field test data are diagnosed. The method can be used to direct the analysis and elimination of interference signal in field ultrasonic detection.
关键词(KeyWords):
GIS;超声波;带电检测;局部放电;干扰信号
GIS;ultrasonic;live detection;partial discharge;interference signal
基金项目(Foundation):
作者(Author):
杜伟,杨勇,梅冰笑,董雪松,邵先军
DU Wei,YANG Yong,MEI Bingxiao,DONG Xuesong,SHAO Xianjun
DOI: 10.19585/j.zjdl.2016.10.001
参考文献(References):
- [1]司文荣,黄华,傅晨钊,等.超声检测进行气体绝缘组合电器典型绝缘缺陷识别[J].高压电器,2011,47(12):11-18.
- [2]LUNDGAARD L E.Partial dischargeⅩⅢ:Acoustic partial discharge detection-fundamental considerations[J].IEEE Electrical Insulation Magazine,1992,8(4):25-31.
- [3]李燕青,陈志业,刘云鹏,等.超声波法进行变压器局部放电模式识别的研究[J].中国电机工程学报,2003,23(2):108-111.
- [4]李颖.GIS局部放电超声检测技术的研究及应用[D].大连:大连理工大学,2014.
- [5]刘君华,姚明,黄成军,等.采用声电联合法的GIS局部放电定位试验研究[J].高电压技术,2009,35(10):2458-2463.
- [6]张红菊.稀土超磁致伸缩电流互感器的研究[D].西安:中国科学研究院西安光学精密仪器研究所,2008.